| Plan Review Notes For Permit 17050392 |
| Permit Number |
17050392 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-31 13:13:29 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | COMMENTS: | | | 1. LIGHTING IN CLOTHES CLOSET WITH OPEN LAMPS ARE NOT | | | PERMITTED. PROVIDE CORRECTION. NEC 410.16 (B) , FBC R | | | E4003.12 | | | 2. SHOW AFCI PROTECTION OF ANY NEW OR ALTERED CIRCUITS. | | | NEC 210.12 , FBC R E3902.12 | | | 3. SHOW DEDICATED OUTLET CIRCUIT FOR BATHROOM GFCI | | | RECEPTACLES. NEC 210.11(C)(3) , FBC R E3703.4 | | | 4. SHOW ALL REQUIRED OUTLETS IN ALTERED BEDROOM FOR | | | FLOOR SPACING. INDICATE ANY EXISTING OUTLETS. NEC | | | 210.52 , FBC R E3901.2 | | | 5. PROVIDE CORRECTION FOR SYMBOL DESCRIPTION IN LEGEND | | | FOR SMOKE ALARMS. CURRENT DESCRIPTION SHOWS A SMOKE | | | ALARM WITH A FIRE DAMPER. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|