Plan Review Notes
Plan Review Notes For Permit 17050392
Permit Number 17050392
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-31 13:13:29CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
 COMMENTS:
 1. LIGHTING IN CLOTHES CLOSET WITH OPEN LAMPS ARE NOT
 PERMITTED. PROVIDE CORRECTION. NEC 410.16 (B) , FBC R
 E4003.12
 2. SHOW AFCI PROTECTION OF ANY NEW OR ALTERED CIRCUITS.
 NEC 210.12 , FBC R E3902.12
 3. SHOW DEDICATED OUTLET CIRCUIT FOR BATHROOM GFCI
 RECEPTACLES. NEC 210.11(C)(3) , FBC R E3703.4
 4. SHOW ALL REQUIRED OUTLETS IN ALTERED BEDROOM FOR
 FLOOR SPACING. INDICATE ANY EXISTING OUTLETS. NEC
 210.52 , FBC R E3901.2
 5. PROVIDE CORRECTION FOR SYMBOL DESCRIPTION IN LEGEND
 FOR SMOKE ALARMS. CURRENT DESCRIPTION SHOWS A SMOKE
 ALARM WITH A FIRE DAMPER. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  