2017-10-17 13:30:553RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17050357
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLAN SHOWS A FIBERGLASS O/A DUCT AND A
 "PROTECTIVE GRILL". PLEASE SEE SECTION 401.5 AND VERIFY
 THAT THE GRILL WILL PROTECT THE DUCT FROM WATER
 INTRUSION. IF USING A LOUVER IT SHALL COMPLY WITH AMCA
 50 AND SHALL BE WIND RESISTENT, IMPACT RATED, AND A
 FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA MUST BE
 SUBMITTED.
  
 2) PROVIDE THE SIZE OF THE MAIN DUCT TRUCK.
  