| 2017-08-18 18:00:50 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17050357 |
| | 8/18/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE RESUBMITTED MECHANICAL PLAN SHEET HAS A COPIED |
| | ARCHITECT'S SIGNATURE AND SEAL. PLEASE NOTE THAT ALL |
| | PLANS AND DOCUMENTS SUBMITTED FOR PUBLIC RECORD BY AN |
| | ARCHITECT MUST BEAR AN ORIGNAL SIGNATURE AND SEAL- |
| | SECTION 61G1-16.003 FAC. |
| | |
| | 2) THE REQUESTED AC EQUIPMENT IS INCOMPLETE. PLEASE |
| | INDICATE WHICH MODEL NO. IS FOR THE CONDENSER AND WHICH |
| | IS FOR THE AIR HANDLER, AND INDICATE THE COOLING AND |
| | HEATING CAPACITIES IN BTU'S. |
| | |
| | 3) THE OUTSIDE AIR CALCULATION IS NOT IN COMPLIANCE |
| | WITH TABLE 403.3 WHICH REQUIRES 5 CFMS PER PERSON + |
| | 0.06 CFMS PER SQ. FT. PLEASE CORRECT AND NOTE THAT O/A |
| | CFMS ARE GENERALLY NOT MORE THAN 20% OF THE TOTAL |
| | SUPPLY AIR OF A SYSTEM,OR APPROXIMATELY 240 CFMS FOR A |
| | 3-TON SYSTEM. |
| | |
| | 4) THE 10" RETURN IS UNDERSIZED FOR 435 CFMS AT A |
| | TYPICAL FRICTION LOSS OF 0.1" |
| | |
| | 5) REFER TO SECTION 401.5 AND INDICATE HOW THE O/A |
| | INTAKE OPENING WILL BE PROTECTED. |
| | |
| | 6) FLEX DUCTS SHALL NOT BE USED TO CONVEY OUTSIDE AIR |
| | UNLESS CERTIFIED BY THE MANUFACTURER FOR THAT TYPE OF |
| | USE. |
| | |
| | 7) THE INPUT DATA REPORT MUST BE ATTACHED WITH THE |
| | ENERGYGAUGE COMPLIANCE SUBMITTAL- SEE PAGE 1 OF THE |
| | SUBMITTAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |