Plan Review Notes
Plan Review Notes For Permit 17050357
Permit Number 17050357
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-11 17:47:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050357
 5/11/17
  
 RESULTS: DENIED.
  
 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN
 INDICATING MAKE AND MODEL, COOLING AND HEATING
 CAPACITIES, ENERGY EFFICIENCY RATING, TOTAL SUPPLY
 CFMS, AND ELECTRICAL DATA.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.3 AND INDICATE HOW OUTSIDE
 AIR IS BEING PROVIDED TO THE OCCUPIED ROOMS AND SPACES-
 SECTION 403.3.
  
 3) INDICATE THE AIR FLOW IN CFMS AT THE SUPPLY
 DIFFUSERS AND RETURN GRILLS.
  
 4) PROVIDE AN INSTALLATION DETAIL FOR THE AIR HANDLER
 INDICATING HOW THE UNIT WILL BE SUSPENDED.
  
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS IN ACCORDANCE WITH SECTION 307. INDICATE THE TYPE
 AND SIZE OF CONDENSATE PIPING, CONDENSATE PIPING RUN,
 AND DISCHARGE LOCATION.
  
 6) PROVIDE DUCT HANGING AND CONNECTION DETAILS
 COMPLIANT WITH THE SMACNA STANDARDS.
  
 7) ENERGY CALCULATION SUBMITTAL: A) PROVIDE THE COVER
 SHEET. B) PROVIDE THE OWNER/AGENT SIGNATURE ON PAGE 3.
 C) THE CHECKLIST ON PAGE 7 MUST BE FILLED OUT BY THE
 DESIGNER OR ENGINEER.
  
 8) THE AC CALCULATIONS MUST BEAR THE NAME AND SIGNATURE
 OF THE PERSON WHO PREPARED THE CALCULATION- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved