| Date |
Text |
| 2017-05-11 17:47:02 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17050357 |
| | 5/11/17 |
| | |
| | RESULTS: DENIED. |
| | |
| | 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN |
| | INDICATING MAKE AND MODEL, COOLING AND HEATING |
| | CAPACITIES, ENERGY EFFICIENCY RATING, TOTAL SUPPLY |
| | CFMS, AND ELECTRICAL DATA. |
| | |
| | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS IN |
| | COMPLIANCE WITH TABLE 403.3 AND INDICATE HOW OUTSIDE |
| | AIR IS BEING PROVIDED TO THE OCCUPIED ROOMS AND SPACES- |
| | SECTION 403.3. |
| | |
| | 3) INDICATE THE AIR FLOW IN CFMS AT THE SUPPLY |
| | DIFFUSERS AND RETURN GRILLS. |
| | |
| | 4) PROVIDE AN INSTALLATION DETAIL FOR THE AIR HANDLER |
| | INDICATING HOW THE UNIT WILL BE SUSPENDED. |
| | |
| | 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| | PLANS IN ACCORDANCE WITH SECTION 307. INDICATE THE TYPE |
| | AND SIZE OF CONDENSATE PIPING, CONDENSATE PIPING RUN, |
| | AND DISCHARGE LOCATION. |
| | |
| | 6) PROVIDE DUCT HANGING AND CONNECTION DETAILS |
| | COMPLIANT WITH THE SMACNA STANDARDS. |
| | |
| | 7) ENERGY CALCULATION SUBMITTAL: A) PROVIDE THE COVER |
| | SHEET. B) PROVIDE THE OWNER/AGENT SIGNATURE ON PAGE 3. |
| | C) THE CHECKLIST ON PAGE 7 MUST BE FILLED OUT BY THE |
| | DESIGNER OR ENGINEER. |
| | |
| | 8) THE AC CALCULATIONS MUST BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON WHO PREPARED THE CALCULATION- SECTION |
| | 107.2.1 WPB AMENDMENTS TO THE FBC. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |