Plan Review Notes
Plan Review Notes For Permit 17050357
Permit Number 17050357
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-23 15:18:43JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1ST REVIEW: FBC 2014
  
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA.
 THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA
 SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT
 IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
 ASHRAE 90.1 8.4.2 RECEPTACLE CONTROL.
  
 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT LEAST 50% OF ALL
 125 VOLT 15- AND 20-AMPERE RECEPTACLES, INCLUDING THOSE
 INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE
 FOLLOWING
 SPACE TYPES:
  
 A. PRIVATE OFFICES
 B. OPEN OFFICES
 C. COMPUTER CLASSROOMS
  
 SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT
 SHALL
 FUNCTION ON:
  
 A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL
 DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC
 PROGRAMMED
 TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL BE PROVIDED
 FOR AREAS OF NO MORE THAN 25,000 FT2 BUT NOT MORE
 THAN ONE FLOOR, OR
 B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR
 C. A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES
 THE AREA IS UNOCCUPIED.
  
  