| 2017-05-16 10:22:47 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050350 |
| | ADD: 600 NORTHPOINT PKWAY/ REPLACEMENT OF ROOF TOP A/C |
| | UNIT |
| | CONT: FLORIDA MECHANICAL LLC |
| | TEL: 561-261-4651 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 16, 2017 |
| | ACTION: DENIED |
| | |
| | 1) IT WOULD APPEAR THAT JOSEPH F. MINICUZZI P. E. IS |
| | THE ENGINEER FOR THE PROJECT AND MAHMOUD MAAMOURI THE |
| | DELEGATE ENGINEER. THE ENGINEER FOR THE PROJECT WILL |
| | NEED TO REVIEW THE DELEGATE ENGINEERS SUBMITTAL AND |
| | REVIEW AND APPROVE WITH A SHOP DRAWING STAMP OF |
| | APPROVAL. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) THIS IS EITHER A CASE OF THE WIND DESIGN DOCUMENTS |
| | NEED TO BE SIGNED AND SEALED ( BY AN ENGINEER) |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS OR THE DESIGNER OF |
| | RECORD TO REVIEW THE COMPUTER GENERATED CALCULATIONS ( |
| | BY THE DELEGATE ENGINEER) AS PART OF THE REVIEW PROCESS |
| | AND IF IN AGREEMENT APPLY HIS SHOP DRAWING STAMP OF |
| | APPROVAL. FL 61G-15-30.006 (3) THE DELEGATED |
| | ENGINEERING. |
| | |
| | 4) THERE IS BOTH A UNKNOWN AND DISCREPANCY BETWEEN THE |
| | S-1 SHEET AND CURB PRODUCT DATA SUBMITTAL. THE S1 SHEET |
| | UNDER THE HEADING MECHANICAL UNIT ROOF TOP ATTACHMENT |
| | INDICATES (14) #12 SMS PER BRACKET EQUALLY SPACED, HOW |
| | MANY BRACKETS, TOTAL. WHEREAS IN THE CURB PRODUCT DATA |
| | DOCUMENTS SHEET S4 DATED 3/29/17 INDICATES THE BRACKET |
| | TO THE UNIT AND CURB W/ #12 OR ? INCH SELF ?DRILLING |
| | SCREWS. THE CLIP ONLY SHOWS A TOTAL OF 6 HOLES OR ONLY |
| | 3 FASTENERS PER SIDE WHERE THE S1 SHEET WOULD HAVE 7 |
| | FASTENERS PER SIDE. |
| | DISCREPANCY IN PLANS? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |