2017-05-15 18:55:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS DO NOT SPECIFY IF THE POOL HEATER IS NEW
 OR EXISTING. SHOW THE POOL HEATER AND WIRE SIZES FOR IT
 ON THE ELECTRICAL SCHEMATIC DIAGRAM. FBC 107.2.1
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPCIFICATIONS FOR THE POOL HEATER. FBC 107.2.1 &
 FBCR-E4206.12
  
 3) SUBMIT ELECTRICAL LOAD CALCULATIONS FOR THE DWELLING
 TO SHOW THAT THE EXISTING SERVICE IS ADEQUATE FOR THE
 NEW POOL EQUIPMENT. FBCR-E3602.2
  
 4) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION
 R403.9.3 FOR THERMAL POOL COVER.
  
  