| 2017-05-18 14:07:31 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050329 |
| | ADD: 4801 DREHER TRAIL NORTH |
| | CONT: GAST CONSTRUCTION |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 18, 2017 |
| | ACTION: DENIED |
| | |
| | 1) FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION |
| | IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016. |
| | PROJECT IS LOCATED IN AN A7 FLOOD ZONE, BASE FLOOD AT |
| | ELEVATION 12.00 FT. NGVD THE MINIMUM SLAB ELEVATION IS |
| | 13.00 FT. NGVD. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 2) SHEET A3.1 SHOWS AN ELEVATION OF THE FINISH SLAB AT |
| | 13.0 FEET. PLEASE INDICATE NGVD. THE SHEET S-1 SHOWS |
| | THE INTERIOR OF THE RESTROOMS AND THE INFORMATION BOOTH |
| | FLOOR SLABS AT 0 ?-0? WHICH IS EQUAL TO THE 13.0 FT. |
| | NGVD. THE S-1 PLAN ALSO SHOWS THE EXTERIOR FLOOR SLAB |
| | WITH 1/8 SLOPE / FOOT OR ON THE WEST SIDE OF THE |
| | BUILDING APPROXIMATELY A FINISH FLOOR ELEVATION OF 12 |
| | FOOT 10 INCHES, BELOW THE REQUIRED 13-0 FINISH FLOOR |
| | ELEVATION. THIS BUILDING COULD NOT EVER BE TOTALLY |
| | ENCLOSED. PLEASE INDICATE THE SLOPES FROM THE RESTROOMS |
| | AS WELL, TO SHOW COMPLIANCE WITH 2014 ACCESS. CODE |
| | 403.3 SLOPE. THE RUNNING SLOPE OF WALKING SURFACES |
| | SHALL NOT BE STEEPER THAN 1:20. THE CROSS SLOPE OF |
| | WALKING SURFACES SHALL NOT BE STEEPER THAN 1:48. THE |
| | A/C PAD HAS TO ALSO BE A MINIMUM OF 13.0 FT. NGVD. |
| | 3) THE USE OF THIS STRUCTURE IS BEING DECLARED A |
| | BUSINESS OCCUPANCY . A LETTER FROM LEE & SHAHAMAD |
| | INDICATES THIS STRUCTURE TO BE AN INFORMATION BOOTH AND |
| | TO PROVIDE SUPPORT FOR THE EXISTING MINI-GOLF COURSE |
| | AND FOR FUTURE DEVELOPMENT OF PLANNED SCIENCE TRAIL AND |
| | OUTDOOR ACTIVITIES. IS THIS TRULY A BUSINESS OCCUPANCY? |
| | THE REASON THE QUESTION IS ASKED IS THE SUBMITTED SOILS |
| | REPORT FOR THE SAME BUILDING LIST THIS BUILDING AS A |
| | CONCESSION AREA BORING B-7 & B-8. ADDITIONAL |
| | INFORMATION IS REQUIRED 107.2.1.3. |
| | 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | |
| | 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | 6) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 7) FLAT ROOFS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. |
| | 8) SHEET A1.2 SHOWS THE BOTTOM OF THE MIRRORS |
| | REFLECTIVE SURFACE AT AN ELEVATION OF 3 FOOT 7 INCHES |
| | OR 43 INCHES. PLEASE REFER TO THE 2014 FBC-ACCESS. CODE |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |