| Plan Review Notes For Permit 17050307 |
| Permit Number |
17050307 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-10 12:12:02 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050307 | | | 5/10/17 | | | | | | 1) SECTION 606.2.1 RETURN AIR SYSTEMS. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR | | | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM | | | (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF | | | ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR | | | CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND | | | APPLIANCES. | | | | | | PLEASE CORRECT THE PLAN TO SHOW THE LOCATION OF THE | | | REQUIRED DEVICE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|