| Plan Review Notes For Permit 17050294 |
| Permit Number |
17050294 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-09 10:36:45 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THE UNDERGROUNG FRIE LINE SHALL BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24, STANDARD FOR THE INSTALLATION | | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, | | | 2010 EDITION. | | | | | | | | | 2) PLEASE PROVIDE MANUFACTURES SPECIFICATION SHEET FOR | | | ALL UNDERGROUND EQUIPMENT FOR FIRE INSPECTOR REVIEW AND | | | VERIFICATION AT THE TIME OF INSPECTION. | | | | | | | | | 3) DO NOT COVER OVER PRIOR TO FIRE INSPECTION. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|