| Plan Review Notes For Permit 17050276 |
| Permit Number |
17050276 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-05 13:04:34 | 8264 NORTHLAKE BOULEVARD | | | PERMIT #17050276 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS DO NOT INDICATE THE USE/OCCUPANCY OF THE | | | STRUCTURE. | | | | | | PLANS DO NOT INDICATE THE CANDELA OF THE APPLIANCES OR | | | CLASS/STYLE OF WIRING. | | | | | | PLANS INDICATE A SMOKE DETECTOR IN ONE STORAGE ROOM; | | | HOWEVER, THE OTHER TWO ROOMS HAVE NO INITIATING | | | DEVICES. | | | | | | A SINGLE HORN-STROBE DEVICE DOES NOT APPEAR TO PROVIDE | | | COVERAGE IN THE LARGEST ROOM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|