| Plan Review Notes For Permit 17050223 |
| Permit Number |
17050223 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-07-13 16:41:09 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- INSPECTION REQUIRED FOR PROPOSED DRAINAGE PLAN. | | | 2- PROVIDE CORRECT AREA CALCULATION ON SHEET A-1. | | | 3- PROVIDE SURVEY W/ ORIGINAL SEAL/SIGNATURE. | | | 4- REVISE CARBON MONOXIDE ALARMS LOCATION. | | | 5- REVISE WINDOW/DOOR BUCK DETAILS. BEVELED BUCKS ARE | | | NOT ALLOWED AND THE BUCK NEEDS TO PROVIDE FULL SUPPORT | | | TO THE WINDOW/DOOR FRAME. | | | 6- REVISE ENERGY CALCULATIONS: (A) COMPLETE | | | INFORMATION: OWNER NAME, PERMIT OFFICE, JURISDICTION | | | NUMBER (604700). (B) NEED CALCULATIONS FOR THE ACTUAL | | | ORIENTATION OF THE BUILDING, NOT WORST CASE. C) MISSING | | | INFORMATION ABOUT ADJACENT WALL. D) REVISE TYPE AND | | | MATERIALS OF THE ROOF INFORMATION. E) REVISE DOORS | | | INFORMATION. NO INSULATED DOORS. REVISE SIZE ALSO. F) | | | DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW | | | AREA. G) REVISE THE WINDOWS INFORMATION. THE OVERHANG | | | SEPARATION DOESN'T MATCH PLANS. H) PROVIDE | | | MANUFACTURER'S SPECIFICATIONS SHOWING THE SPECIFIED | | | U-FACTOR AND SHGC FACTOR FOR DOORS AND WINDOWS. |
|