| Plan Review Notes For Permit 17050223 |
| Permit Number |
17050223 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-02 09:25:29 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ACCORDING TO THE ENERGY CALCULATIONS SUBMITTED, IT | | | LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE DONE | | | BASED ON THE WORST CASE SCENARIO (SEE BUILDING REVIEW | | | COMMENTS). THE EQUIPMENT SIZING NEEDS TO BE CALCULATED | | | BASED ON THE ACTUAL ORIENTATION OF THE BUILDING AS | | | REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). REVISE CALCULATIONS AND PROVIDE | | | COMPLETE CALCULATIONS NOT JUST THE SUMMARY SHEET. | | | | | | 2- PROVIDE COMPLETE A/C PLAN. NOTE: A/C PLAN TO INCLUDE | | | THE EQUIPMENT MANUFACTURER AND MODEL SPECIFIED ON THE | | | EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10) CITY | | | AMENDMENTS. | | | | | | NOTE: | | | *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING | | | EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|