Plan Review Notes
Plan Review Notes For Permit 17050213
Permit Number 17050213
Review Stop E
Sequence Number 2
Notes
Date Text
2017-07-14 16:54:50PLAN REVIEW NOTES AHVE BEEN ADDRESSED ON PLANS WITH
 NOTES JLEAHY
2017-07-14 09:33:36CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ALL OUTLETS IN GARAGE SHALL BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8; FBC 3902.2
 2. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 3. SHOW ON PLAN THE LOCATION OF THE ELECTRICAL SERVICE
 AND INDICATE IF THE SERVICE WILL BE OVERHEAD OR
 UNDERGROUND TO CONFIRM CODE COMPLIANCE. FBC 107.3.5,
 FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 6. ELECTRICAL RISER SHOWS THE CONDUIT FROM DISCONNECT
 TO INTERIOR PANEL WITH THREE #1 COPPER CONDUCTORS. AN
 EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN THIS
 CONDUIT. PROVIDE CORRECTION. NEC 250.122; FBC RE3908.7
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 8. PROVIDE PER CODE: "ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION". NEC 210.12, FBC
 RE3902.12
 9. LIGHTING IN MASTER CLOSET IS NOT SPECIFIED, PROVIDE
 NOTE TO COMPLY WITH NEC 410.16. NEC 410.16; FBC
 RE4003.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
2017-07-05 18:47:46NEW DRAWINGS SUBMITTED. JG.