| Date |
Text |
| 2017-07-14 16:54:50 | PLAN REVIEW NOTES AHVE BEEN ADDRESSED ON PLANS WITH |
| | NOTES JLEAHY |
| 2017-07-14 09:33:36 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ALL OUTLETS IN GARAGE SHALL BE GFCI PROTECTED. |
| | PROVIDE CORRECTION. NEC 210.8; FBC 3902.2 |
| | 2. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | 3. SHOW ON PLAN THE LOCATION OF THE ELECTRICAL SERVICE |
| | AND INDICATE IF THE SERVICE WILL BE OVERHEAD OR |
| | UNDERGROUND TO CONFIRM CODE COMPLIANCE. FBC 107.3.5, |
| | FBC 107.2.1 |
| | 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 6. ELECTRICAL RISER SHOWS THE CONDUIT FROM DISCONNECT |
| | TO INTERIOR PANEL WITH THREE #1 COPPER CONDUCTORS. AN |
| | EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN THIS |
| | CONDUIT. PROVIDE CORRECTION. NEC 250.122; FBC RE3908.7 |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 8. PROVIDE PER CODE: "ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION". NEC 210.12, FBC |
| | RE3902.12 |
| | 9. LIGHTING IN MASTER CLOSET IS NOT SPECIFIED, PROVIDE |
| | NOTE TO COMPLY WITH NEC 410.16. NEC 410.16; FBC |
| | RE4003.12 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| 2017-07-05 18:47:46 | NEW DRAWINGS SUBMITTED. JG. |