| Plan Review Notes For Permit 17050212 |
| Permit Number |
17050212 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-11 12:50:23 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050212 | | | 5/11/17 | | | | | | 1) PROVIDE A PLAN THAT SHOWS THE LOCATION OF THE | | | CONDENSER ON THE ROOF, INDICATE THE FUNCTION OF THE | | | CONDENSER, AND PROVIDE AN EQUIPMENT SCHEDULE. | | | | | | 2) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE | | | CONDENSER TO THE ROOF STRUCTURE- SECTION 301.15. | | | | | | 3) BECAUSE THIS IS A SEPARATE PERMIT FROM THE PRIMARY, | | | THE MECHANICAL CONTRACTOR MUST SUBMIT A COMPLETE PERMIT | | | APPLICATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|