| Date |
Text |
| 2017-05-30 07:37:29 | 05/31/17 ACCORDING TO PLANS ON PERMIT #04070599 THIS |
| | PROPERTY IS FOR ONE SINGLE FAMILY RESIDENCE ONLY. NOT |
| | COMMERCIAL USE. NOT TENANT SEPARATION REQUIRED. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | 1- AFTER PLANS ARE REVISED (SEE ZONING COMMENTS) BRING |
| | THEM TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT |
| | FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND |
| | COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE |
| | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- INFORMATION SHOWN ON WALL SECTION 3 ON SHEET A-2.1 |
| | DOESN'T MATCH INFORMATION SHOWN ON WALL SECTION "A" AND |
| | ON ROOF SHEATHING AND WALL SHEATHING NOTES SHOWN ON |
| | SHEET S-1. REVISE PLYWOOD SHEATHING THICKNESS TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- ROOF SHEATHING NOTE ON SHEET S-1: SEC. R803.2.3.1 |
| | FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS. ROOF |
| | SHEATHING NOTE ON SHEET S-1 SPECIFIES 6D NAILS. |
| | ENGINEER OF RECORD TO PROVIDE CALCULATIONS (BASED ON |
| | THE HEIGHT AND BUILDING EXPOSURE "D" OF THIS BUILDING) |
| | SHOWING THAT THE PROPOSED ROOF SHEATHING NAIL TYPE, |
| | SIZE AND SPACING IS EQUAL OR BETTER THAN THE |
| | SPECIFICATIONS REQUIRED BY SEC. R803.2.3.1. |
| | |
| | 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R3 |
| | SUBMITTED: |
| | A) SELECTED ASSEMBLY (W-1) IS FOR AN INSULATED FLAT |
| | ROOF ASSEMBLY. PLANS SUBMITTED DON'T SPECIFIED |
| | INSULATED FLAT ROOF ASSEMBLY. CLARIFY IF INSTALLING |
| | INSULATED ASSEMBLY OR NON-INSULATED ASSEMBLY. REVISE |
| | PLANS AND SELECTED ASSEMBLY AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) THERE IS A HANDWRITTEN NOTE ON PAGE 4 OF 14 ON THE |
| | SELECTED ASSEMBLY (W-1) SPECIFYING 1/8" / FT. SLOPE |
| | TAPERED PERLITE INSULATION. SEC. R905.11.1 |
| | FBC-RESIDENTIAL AND SECOND FLOOR ROOF PLAN ON SHEET |
| | A-2.1 REQUIRES 1/4" PER FT MINIMUM ROOF SLOPE. REVISE |
| | AS REQUIRED. |
| | |
| | C) INFORMATION SHOWN ON RAS 117 CALCULATIONS PREPARED |
| | BY TURQUOISE ENGINEERING AND FLORIDA PRODUCT APPROVAL |
| | FL16709-R3 SUBMITTED DON'T MATCH. ENGINEER CALCULATIONS |
| | ARE REFERRING TO APPROVED ASSEMBLY W-3 WHILE FLORIDA |
| | PRODUCT APPROVAL SUBMITTED IS FOR APPROVED ASSEMBLY |
| | W-1. REVISE AS REQUIRED TO MATCH AND COORDINATE WITH |
| | ITEM #4(A) ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- REVISE ENERGY CALCULATIONS SUBMITTED; |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM, |
| | INCLUDING THE NAME OF THE BUILDER. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) REVISE THE CEILING INFORMATION ON ITEM #10 TO MATCH |
| | PLANS SUBMITTED. PLANS CALL FOR A VENTED CEILING NOT |
| | UNVENTED. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4 TO |
| | MATCH PLANS. THERE ARE NOT TWO WINDOWS ON THE SW WALL. |
| | SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | D) REVISE THE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4. |
| | SEE PLANS AND PRODUCT APPROVAL AND REVIEW AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | ATTACHMENT OF THE A/C CONDENSER UNIT AS SPECIFIED ON |
| | SECOND FLOOR PLAN ON SHEET A-2.1. EQUIPMENT NEEDS TO BE |
| | FASTENED TO RESIST THE WIND LOADS OF SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: KEEP IN MIND THAT EXTERIOR WALLS |
| | FRAMING IS STEEL STUDS. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |