| 2017-05-15 14:05:23 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1. TYPICAL WALL SECTION ON PLAN PAGE A-1 DENOTES THE |
| | INSTALLATION OF 5/8" STUCCO. PROVIDE A WATER RESISTIVE |
| | BARRIER PER R703.6.3 WHEN INSTALLING THE REQUIRED METAL |
| | LATH. |
| | 2. PROVIDE A FASTENER SCHEDULE FOR THE CONNECTION OF |
| | NEW WOOD FRAMED WALLS TO EXISTING CONCRETE COLUMNS. |
| | |
| | R703.6.3 WATER-RESISTIVE BARRIERS. |
| | WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| | IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| | SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| | VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| | EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| | INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| | THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| | AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| | R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| | BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| | |