| 2017-05-08 08:45:58 | COMMERCIAL COOKING EQUIPMENT SHALL COME INTO COMPLIANCE |
| | WITH THE BELOW CODE. |
| | NFPA 1-50.4.8,1 2012 EDITION SYSTEM ANNUNCIATION: UPON |
| | ACTIVATION OF AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM, |
| | AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED |
| | TO SHOW THAT THE SYSTEM HAS ACTIVATED. [96:10.6.1] |
| | |
| | NFPA1-50.4.8.2: WHERE A FIRE ALARM SIGNALING SYSTEM IS |
| | SERVING THE OCCUPANCY WHERE THE EXTINGUISHING SYSTEM IS |
| | LOCATED, THE ACTIVATION OF THE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM SHALL ACTIVATE THE FIRE ALARM |
| | SIGNALING SYSTEM. [96:10.6.2]. |
| | |
| | NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT |
| | INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE |
| | COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS |
| | CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S), |
| | SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE |
| | SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A |
| | QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. |
| | |
| | 10.18.2.4.1 VERIFICATION SHALL ENSURE THAT THE |
| | INSTALLED SYSTEM INCLUDES ALL COMPONENTS AND FUNCTIONS, |
| | THAT THOSE COMPONENTS AND FUNCTIONS ARE INSTALLED AND |
| | OPERATE AS REQUIRED, THAT THE SYSTEM HAS BEEN 100 |
| | PERCENT ACCEPTANCE TESTED IN ACCORDANCE WITH CHAPTER |
| | 14, AND THAT ALL REQUIRED DOCUMENTATION HAS BEEN |
| | PROVIDED TO THE SYSTEM OWNER. |
| | |
| | |