| Date |
Text |
| 2017-05-05 14:12:04 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- THE LANDING ON THE EXTERIOR SIDE OF THE ENTRY DOOR |
| | DOESN'T COMPLY WITH THE MINIMUM DIMENSION REQUIRED BY |
| | SEC. R311.3 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | ENGINEER OF RECORD TO REVISE DIMENSION ON SHEET #1 AND |
| | #2. |
| | |
| | 2- INFORMATION ON DETAIL 5 TYPICAL PIER FOOTING IS |
| | INCOMPLETE. IT'S MISSING THE FOOTING SIZE, THIS IS NOT |
| | A CONTINUOUS FOOTING. THEREFORE THERE IS NO CONTINUOUS |
| | (2)#5. REVISE AS REQUIRED. PROVIDE CORRECT FOOTING |
| | INFORMATION. PROVIDE SPECIFICATIONS FOR THE FILLED |
| | CELLS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | THE ATTACHMENT OF THE PORCH TO THE PIER. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE VENTILATION REQUIREMENTS OF SEC. |
| | R408 FBC-RESIDENTIAL FOR THE REVISED PORCH AREA. NOTE: |
| | MAKE SURE CROSS VENTILATION FOR THE STEM WALL IS NOT |
| | BLOCKED. |
| | |
| | 4- REVISED FOUNDATION PLAN. NEED VERTICAL REINFORCEMENT |
| | IN ALL CORNERS AS REQUIRED BY SEC. R609.3.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- QUALITY OF THE PRINTS SUBMITTED IS NOT GOOD. THEY |
| | HAVE PRINTING DARK LINES THAT ARE BLOCKING THE |
| | INFORMATION. PROVIDE CLEAR COPIES. SEC. 107.2.1.4 CITY |
| | AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |