| Plan Review Notes For Permit 17050074 |
| Permit Number |
17050074 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-30 10:59:23 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050074 | | | 6/30/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) CONTRARY TO THE SUBMITTED RESPONSE NARRATIVE FROM | | | THE ARCHITECT MOODY NOLAN INC., THE PLANS ARE STILL | | | INDICATING DEMOLITION OF THE EXISTING RTU AND | | | INSTALLATION OF A NEW JOHNSON CONTROLS SYSTEM. IF THE | | | EXISTING YORK UNIT IS TO REMAIN IN PLACE AS THE | | | NARRATIVE SEEMS TO INDICATE, THEN PLEASE REVISE THE | | | PLANS ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|