Plan Review Notes
Plan Review Notes For Permit 17050074
Permit Number 17050074
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-25 17:34:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050074
 5/25/17
  
 RESULTS: DENIED.
  
 1) THE AC COOLING AND HEATING CALCULATIONS ON SHEET
 M04.01 INDICATE THE RTU SELECTED IS UNDERSIZED IN BOTH
 COOLING AND HEATING CAPACITY- SEE AC SCHEDULE ON SHEET
 M0.01.
  
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA, AND
 STRUCTURAL DETAILS BY A FL. REGISTERED ENGINEER FOR
 INSTALLATION OF THE NEW RTU- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER