| Plan Review Notes For Permit 17050074 |
| Permit Number |
17050074 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-18 08:10:44 | 1771 OR 1751 PALM BEACH LAKES BOULEVARD - #W311 | | | PERMIT #17050074 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS OF THE PERMIT IS INDICATED AS 1771 PALM | | | BEACH LAKES BOULEVARD; HOWEVER, THE PERMIT APPLICATION | | | AND PLANS INDICATE AN ADDRESS OF 1751 PALM BEACH LAKES | | | BOULEVARD. | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC | | | SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION | | | DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA | | | FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL." | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|