| Plan Review Notes For Permit 17050074 |
| Permit Number |
17050074 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-02 09:12:31 | PLANS NOT SIGNED AND SEALED PER FS. 06/02/17 JP | | 2017-06-01 14:34:48 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | 1ST REVIEW COMMENTS: | | | | | | 1. SHEET E03.01, KEY NOTE 6, STATES THAT THE EXIT AND | | | EMERGENCY LIGHTS SHOULD BE ON CIRCUIT A-1. NEC REQUIRES | | | THAT THESE ITEMS BE WIRED TO THE NORMAL LIGHTING | | | CIRCUIT IN THE AREA. PROVIDE CORRECTION. NEC 700.12(F) | | | 2. PROVIDE SHORT CIRCUIT CALCULATION FOR THE AVAILABLE | | | FAULT CURRENT AT THE SERVICE. AN ASSUMED AMOUNT IS NOT | | | ACCEPTABLE. NEC 110.10 | | | 3. PROVIDE MANUFACTURERS SPEC SHEET FOR SWITCHGEAR | | | "IFS" TO VERIFY LISTING. NEC 110.3 | | | 4. ADDRESS NEEDS VERIFICATION. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|