| 2017-05-26 13:59:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | REVIEW #1 (FIRST PERMIT APPLICATION SUBMITTAL) |
| | |
| | 1. ARCHITECT BUSINESS LICENSE (26001393) IS REQUIRED TO |
| | BE A PART OF THE TITLE BLOCK, FS481, FAC61G15. ADD TO |
| | ALL REVISED PAGES (IT APPEARS ALL SHEETS WILL BE |
| | REVISED DUE TO ADDRESS CORRECTION). |
| | |
| | 2. PLAN IS FOR 1751 PALM BEACH LAKES W311, APPLICATION |
| | IS 1771 PALM BEACH LAKES W311. VERIFY ADDRESS; REVISE |
| | PLAN ACCORDINGLY. OUR RECORDS SHOW THAT THIS SPACE WAS |
| | PREVIOUSLY "KENNETH COLE"; IS THIS CORRECT? |
| | |
| | 3. PROVIDE PRODUCT APPROVAL FOR THE PROPOSED EXTERIOR |
| | DOORS AND STOREFRONT, FBC B 1609. |
| | |
| | 4. FBC B 603.1, DETAIL M A04.1, REVISE PLAN TO CLARIFY |
| | WHAT "PLANKING SF-90" IS. IF THIS IS A COMBUSTIBLE, |
| | PROVIDE MORE INFORMATION TO SHOW COMPLIANCE WITH FBC B |
| | 801, 803. |
| | |
| | 5. VARIOUS PAGES APPEAR TO SHOW MYLAR AND TINTING |
| | INSTALLED OVER IMPACT GLASS PRODUCTS. VERIFY WITH |
| | MANUFACTURER THAT THIS DOES NOT AFFECT THE IMPACT AND |
| | PRESSURE REQUIREMENTS. NO RESPONSE NECESSARY OTHER THAN |
| | TO ACKNOWLEDGE (IN RESPONSE LETTER) AND REVISE IF |
| | NECESSARY; ISSUED AT APPLICANT'S RISK. |
| | |
| | 6. THERE ARE A NUMBER OF REDLINED ITEMS WHICH APPEAR TO |
| | BE FROM THE LANDLORD. AT LEAST ONE STATES "REVISE AND |
| | RESUBMIT" (A08.3). |
| | |
| | NO ONE OTHER THAN THE DESIGN PROFESSIONAL CAN ALTER THE |
| | DESIGN OF THAT PROFESSIONAL, FS471,481. IT IS NOT CLEAR |
| | HOW SOME ITEMS AFFECT CODE COMPLIANCE - FOR INSTANCE, |
| | LED PANEL EMILINATED ON SHEET A08.3. |
| | |
| | REVISE THE PLAN TO INCORPORATE THE CHANGES WHICH AFFECT |
| | CODE COMPLIANCE. WHEN RESUBMITTING, PROVIDE "CLEAN" |
| | PAGES. ONE PDF WITH A REVIEW STAMP BY THE LANDLORD IS |
| | ONE WAY TO DEMONSTRATE REVIEW; ANOTHER OPTION WOULD BE |
| | A COVER LETTER REFERRING TO SPECIFIC PLANS AND PAGES. |
| | |
| | 7. DETAIL A 08.5 AND POSSIBLY OTHER LOCATIONS, THERE IS |
| | A STATEMENT REGARDING EXTERIOR GRADE PLYWOOD. FBC B |
| | 603.1, CLARIFY AMOUNT OF PLYWOOD PROPOSED WHICH IS NOT |
| | FRT (OTHER THAN CABINETRY; NOTE IS ON STOREFRONT |
| | DETAILS PAGE), REVISE PLAN TO INCORPORATE APPLICABLE |
| | EXCEPTION, OR REMOVE OR MODIFY NOTE. (NOTE THAT DETAIL |
| | K-A12.1 SPECS FRT.) |
| | |
| | 8. SEPARATE PERMITS (APPLICATIONS, PLANS, REVIEWS, |
| | FEES) REQUIRED FOR SIGNS. |
| | |
| | |