Plan Review Notes
Plan Review Notes For Permit 17050074
Permit Number 17050074
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-26 13:59:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 REVIEW #1 (FIRST PERMIT APPLICATION SUBMITTAL)
  
 1. ARCHITECT BUSINESS LICENSE (26001393) IS REQUIRED TO
 BE A PART OF THE TITLE BLOCK, FS481, FAC61G15. ADD TO
 ALL REVISED PAGES (IT APPEARS ALL SHEETS WILL BE
 REVISED DUE TO ADDRESS CORRECTION).
  
 2. PLAN IS FOR 1751 PALM BEACH LAKES W311, APPLICATION
 IS 1771 PALM BEACH LAKES W311. VERIFY ADDRESS; REVISE
 PLAN ACCORDINGLY. OUR RECORDS SHOW THAT THIS SPACE WAS
 PREVIOUSLY "KENNETH COLE"; IS THIS CORRECT?
  
 3. PROVIDE PRODUCT APPROVAL FOR THE PROPOSED EXTERIOR
 DOORS AND STOREFRONT, FBC B 1609.
  
 4. FBC B 603.1, DETAIL M A04.1, REVISE PLAN TO CLARIFY
 WHAT "PLANKING SF-90" IS. IF THIS IS A COMBUSTIBLE,
 PROVIDE MORE INFORMATION TO SHOW COMPLIANCE WITH FBC B
 801, 803.
  
 5. VARIOUS PAGES APPEAR TO SHOW MYLAR AND TINTING
 INSTALLED OVER IMPACT GLASS PRODUCTS. VERIFY WITH
 MANUFACTURER THAT THIS DOES NOT AFFECT THE IMPACT AND
 PRESSURE REQUIREMENTS. NO RESPONSE NECESSARY OTHER THAN
 TO ACKNOWLEDGE (IN RESPONSE LETTER) AND REVISE IF
 NECESSARY; ISSUED AT APPLICANT'S RISK.
  
 6. THERE ARE A NUMBER OF REDLINED ITEMS WHICH APPEAR TO
 BE FROM THE LANDLORD. AT LEAST ONE STATES "REVISE AND
 RESUBMIT" (A08.3).
  
 NO ONE OTHER THAN THE DESIGN PROFESSIONAL CAN ALTER THE
 DESIGN OF THAT PROFESSIONAL, FS471,481. IT IS NOT CLEAR
 HOW SOME ITEMS AFFECT CODE COMPLIANCE - FOR INSTANCE,
 LED PANEL EMILINATED ON SHEET A08.3.
  
 REVISE THE PLAN TO INCORPORATE THE CHANGES WHICH AFFECT
 CODE COMPLIANCE. WHEN RESUBMITTING, PROVIDE "CLEAN"
 PAGES. ONE PDF WITH A REVIEW STAMP BY THE LANDLORD IS
 ONE WAY TO DEMONSTRATE REVIEW; ANOTHER OPTION WOULD BE
 A COVER LETTER REFERRING TO SPECIFIC PLANS AND PAGES.
  
 7. DETAIL A 08.5 AND POSSIBLY OTHER LOCATIONS, THERE IS
 A STATEMENT REGARDING EXTERIOR GRADE PLYWOOD. FBC B
 603.1, CLARIFY AMOUNT OF PLYWOOD PROPOSED WHICH IS NOT
 FRT (OTHER THAN CABINETRY; NOTE IS ON STOREFRONT
 DETAILS PAGE), REVISE PLAN TO INCORPORATE APPLICABLE
 EXCEPTION, OR REMOVE OR MODIFY NOTE. (NOTE THAT DETAIL
 K-A12.1 SPECS FRT.)
  
 8. SEPARATE PERMITS (APPLICATIONS, PLANS, REVIEWS,
 FEES) REQUIRED FOR SIGNS.
  
  