2017-08-07 09:53:58RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- ELEVATION CERTIFICATE:
 A) THE REVISED ELEVATION CERTIFICATE STILL SHOWS 7.32'
 AS THE FINISH FLOOR ELEVATION FOR THE A/C EQUIPMENT.
 CITY CODE SEC. 94-546(B)(1) REQUIRES FINISH ELEVATION
 TO BE 1 FOOT ABOVE THE BASE FLOOD ELEVATION. THE BASE
 FLOOR ELEVATION FOR FLOOD ZONE A5 IS 7'-0". NEED 8'-0"
 MIN. EQUIPMENT NEEDS TO BE ELEVATED AND THE ELEVATION
 CERTIFICATE NEEDS TO BE REVISED AS WELL.
  
 B) THE REVISED ELEVATION CERTIFICATE NEEDS TO HAVE THE
 SURVEYOR ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS FOR PUBLIC
 RECORDS.
  
  
 2- REVISED SHEETS A-2 AND A-3 ARE MISSING THE
 ENGINEER'S SIGNATURE AND DATE AS REQUIRED BY CHAPTER
 471 F.S WHEN SUBMITTING PLANS FOR PUBLIC RECORDS.
  
  