Plan Review Notes
Plan Review Notes For Permit 17050053
Permit Number 17050053
Review Stop P
Sequence Number 2
Notes
Date Text
2017-05-18 15:01:031ST REVIEW: FBC 2014 5TH EDITION
  
 IRRIGATION COMMENTS: 5/18/17
  
 1. BACKFLOW REQUIRED ON IRRIGATION SYSTEM SEPARATE
 PERMIT REQUIRED FOR BACKFLOW. PER WPB CROSS CONNECTION
 MANUAL PG.19 PAR. I
  
 2. A RAIN SENSOR IS REQUIRED ON IRRIGATION CONTROLS.
 PER FS 373.62
  
 3. SPAY HEADS SHALL BE A MIN OF 12IN" FROM STRUCTURE.
 FBC PL 318.1
  
 4. SHOW LOCATION OF CONTROLS AND RAIN SENSOR. PER WPB
 AMEND TO FBC 107.2.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  