| Plan Review Notes For Permit 17050053 |
| Permit Number |
17050053 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-23 13:29:57 | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1ST REVIEW FBC 2014 EXISTING BUILDING | | | | | | PAGE E.1 | | | | | | E3901.2.1 SPACING. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE | | | IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE | | | OUTLET. | | | | | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET. | | | | | | NEED RISER DIAGRAM AND LOAD CALCULATION INACCORDANCE | | | WITH THE CODES 215.5, 220. | | | | | | E3602.2 SERVICE LOAD. | | | THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND | | | SERVICE DEVICES THAT SERVE 100 PERCENT | | | OF THE DWELLING UNIT LOAD SHALL BE COMPUTED IN | | | ACCORDANCE WITH TABLE E3602.2. UNGROUNDED SERVICE | | | CONDUCTORS AND SERVICE DEVICES THAT SERVE LESS THAN 100 | | | PERCENT OF THE DWELLING UNIT LOAD SHALL BE | | | COMPUTED AS REQUIRED FOR FEEDERS IN ACCORDANCE WITH | | | CHAPTER 37. | | | | | | |
|