Plan Review Notes
Plan Review Notes For Permit 17050053
Permit Number 17050053
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-23 13:29:57 
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 PAGE E.1
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE
 IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET.
  
 NEED RISER DIAGRAM AND LOAD CALCULATION INACCORDANCE
 WITH THE CODES 215.5, 220.
  
 E3602.2 SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT
 OF THE DWELLING UNIT LOAD SHALL BE COMPUTED IN
 ACCORDANCE WITH TABLE E3602.2. UNGROUNDED SERVICE
 CONDUCTORS AND SERVICE DEVICES THAT SERVE LESS THAN 100
 PERCENT OF THE DWELLING UNIT LOAD SHALL BE
 COMPUTED AS REQUIRED FOR FEEDERS IN ACCORDANCE WITH
 CHAPTER 37.
  
  