| Plan Review Notes For Permit 17050036 |
| Permit Number |
17050036 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-05 09:35:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED | | | TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC | | | 107.2.1, FS 471, 481 | | | 2. PER THE WPB AMENDMENTS TO THE FBC, QUALITY OF | | | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A | | | MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR | | | OTHER ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE | | | CORRECTION. CURRENT PLAN SUBMITTED DOES NOT MEET THIS | | | CRITERIA AND IS DIFFICULT TO READ. WPB FBC 107.2.1.4 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|