| 2017-05-16 16:04:53 | EMERGENCY GENERATORS AND STANDBY POWER EQUIPMENT SHALL |
| | COME INTO COMPLIANCE WITH THE BELOW FIRE CODES: |
| | |
| | NFPA 110 STANDARDS FOR EMERGENCY & STANDBY POWER |
| | NFPA 70 NATIONAL ELECTRICAL CODE/NEC. |
| | |
| | NFPA 101-11.8.5, 2012 EDITION EMERGENCY LIGHTING AND |
| | STANDBY POWER. |
| | 11.8.5.1 EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION |
| | 7.9 SHALL BE PROVIDED. 11.8.5.2 REQUIREMENTS FOR |
| | STANDBY POWER SHALL BE AS SPECIFIED IN 11.8.5.2.1 |
| | THROUGH 11.8.5.2.4. |
| | 11.8.5.2.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN |
| | ACCORDANCE WITH ARTICLE 701 OF NFPA 70, NATIONAL |
| | ELECTRICAL CODE, AND NFPA 110, STANDARD FOR EMERGENCY |
| | AND STANDBY POWER SYSTEMS, |
| | SHALL BE PROVIDED. |
| | 11.8.5.2.2 THE STANDBY POWER SYSTEM SHALL HAVE A |
| | CAPACITY AND RATING SUFFICIENT TO SUPPLY ALL EQUIPMENT |
| | REQUIRED TO BE CONNECTED BY 11.8.5.2.4. |
| | 11.8.5.2.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING |
| | SHALL BE PERMITTED IN ACCORDANCE WITH NFPA 70, NATIONAL |
| | ELECTRICAL CODE. |
| | 11.8.5.2.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED |
| | TO THE FOLLOWING: |
| | (1) ELECTRIC FIRE PUMP |
| | (2) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 |
| | FOR SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES |
| | (3) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION |
| | SYSTEMS, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 FOR |
| | SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES |
| | (4) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING |
| | (5) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH |
| | STANDBY POWER TRANSFERABLE TO ANY ELEVATOR |
| | (6) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES |
| | (7) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE |
| | REQUIREMENTS OF SECTION 9.3 |
| | |
| | |
| | |