| Notes |
| Date |
Text |
| 2017-05-23 12:13:47 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | | | NOT SURE WHAT YOUR SYBOLS MEAN PLEASE PLACE A SCHEDULE | | | OF SYMBOLS ON PLANS. | | | | | | NEED TO SHOW ALL WORK RELEATED TO THE KITCHEN REMODEL | | | INCLUDING A PANEL SCHEDULE | | | WHICH SHOWS THE BRANCH CIRCUITS AND SIZES ON THE | | | CIRCUITS. | | | | | | E3901.4.1 WALL COUNTERTOP SPACE. | | | A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL | | | COUNTERTOP SPACE 12 INCHES | | | (305 MM) OR WIDER. RECEPTACLE OUTLETS SHALL BE | | | INSTALLED SO THAT NO POINT ALONG | | | THE WALL LINE IS MORE THAN 24 INCHES (610 MM), MEASURED | | | HORIZONTALLY FROM A | | | RECEPTACLE OUTLET IN THAT SPACE. | | | |
|