2017-07-26 14:30:1713RD REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENTS:
 NOT COMPLIED 3RD REQUEST 1) SUBMIT FIRE STOP DETAILS
 FOR THE PLUMBING PIPE PENETRATIONS THROUGH THE FLOORS
 PER FBC SEC.711.5 & 714.4.1.
  
 NOT COMPLIED 3RD 6) SHT. P201 - PLBG. NOTES #2 -
 TEMPERED WATER IS REQUIRED AT THE LAVATORY PER 2014
 FBC- PLUMBING SEC.416.5, 607.1.
  
 NOT COMPLIED 3RD 7) WATER HAMMER ARRESTORS ARE REQD.
 WHERE QUICK -CLOSING VALVES ARE UTILIZED. 2014
 FBC-PLUMBING SEC.604.9.
 SHOW COMPLIANCE AT DISHWASHER, ICE MAKER AND
 REFRIGERATOR.
  
 NEW COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3. SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 4. THE BRANCH DRAIN FOR BREAKROOM 233 SHALL CONNECT TO
 BUILDING DRAIN DOWNSTREAM OF THE BATHE ROOM GROUP. PER
 FBC PL 912.1
  
 5. THE HORIZONTAL DRY VENT FOR THE WC IS NOT PERMITTED.
 PER FBC ACC 905.3 AND 905.4
  
 6. P-201 NOTE ON RESTROOM PIPING REF. SHOCK ARRESTOR
 SEE DETAIL #6 P-401 , THERE IS NO DETAIL 6 ON P-401
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. P-401 ENLARGED PLAN KEY NOTES #1 PROVIDE
 CALCULATIONS AND MANUFACTURE SPECS FOR GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-401 ENLARGED PLAN KEY NOTES #1 GREASE
 INTERCEPTOR NOT SHOWN ON RISER NETHER IS THE FD-1
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P-401 ENLARGED PLAN KEY NOTES # 3 STATES A 4"
 SANITARY LINE THE RISER SHOWS A 3" PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH