| 2017-07-26 14:30:17 | 13RD REVIEW: FBC 2014 5TH EDITION |
| | |
| | PREVIOUS COMMENTS: |
| | NOT COMPLIED 3RD REQUEST 1) SUBMIT FIRE STOP DETAILS |
| | FOR THE PLUMBING PIPE PENETRATIONS THROUGH THE FLOORS |
| | PER FBC SEC.711.5 & 714.4.1. |
| | |
| | NOT COMPLIED 3RD 6) SHT. P201 - PLBG. NOTES #2 - |
| | TEMPERED WATER IS REQUIRED AT THE LAVATORY PER 2014 |
| | FBC- PLUMBING SEC.416.5, 607.1. |
| | |
| | NOT COMPLIED 3RD 7) WATER HAMMER ARRESTORS ARE REQD. |
| | WHERE QUICK -CLOSING VALVES ARE UTILIZED. 2014 |
| | FBC-PLUMBING SEC.604.9. |
| | SHOW COMPLIANCE AT DISHWASHER, ICE MAKER AND |
| | REFRIGERATOR. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 2. SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 4. THE BRANCH DRAIN FOR BREAKROOM 233 SHALL CONNECT TO |
| | BUILDING DRAIN DOWNSTREAM OF THE BATHE ROOM GROUP. PER |
| | FBC PL 912.1 |
| | |
| | 5. THE HORIZONTAL DRY VENT FOR THE WC IS NOT PERMITTED. |
| | PER FBC ACC 905.3 AND 905.4 |
| | |
| | 6. P-201 NOTE ON RESTROOM PIPING REF. SHOCK ARRESTOR |
| | SEE DETAIL #6 P-401 , THERE IS NO DETAIL 6 ON P-401 |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. P-401 ENLARGED PLAN KEY NOTES #1 PROVIDE |
| | CALCULATIONS AND MANUFACTURE SPECS FOR GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P-401 ENLARGED PLAN KEY NOTES #1 GREASE |
| | INTERCEPTOR NOT SHOWN ON RISER NETHER IS THE FD-1 |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHT. P-401 ENLARGED PLAN KEY NOTES # 3 STATES A 4" |
| | SANITARY LINE THE RISER SHOWS A 3" PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |