2017-06-16 15:20:131ST REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENTS:
 NOT COMPLIED1) SUBMIT FIRE SAFING DETAILS FOR THE
 PLUMBING PIPE PENETRATIONS THROUGH THE FLOORS PER FBC
 SEC.711.5 & 714.4.1.
  
 NOT COMPLIED 3) THE INSTALLATION OF THE GRAB BARS IN
 THE ACCESSIBLE TOILET ROOM SHALL COMPLY WITH 2014
 FBC-ACCESS. SECS.604.5 & 609.4.
  
 NOT COMPLIED 6) SHT. P201 - PLBG. NOTES #2 - TEMPERED
 WATER IS REQUIRED AT THE LAVATORY PER 2014 FBC-
 PLUMBING SEC.416.5, 607.1.
  
 NOT COMPLIED 7) WATER HAMMER ARRESTORS ARE REQD. WHERE
 QUICK -CLOSING VALVES ARE UTILIZED. 2014 FBC-PLUMBING
 SEC.604.9.
  
 NOT COMPLIED 8) THE PLANS SHOW COLD WATER TO THE
 DISHWASHER. CLARIFY. SUBMIT SPECIFICATIONS FOR THE
 DISHWASHER IF IT IS TO BE SUPPLIED WITH COLD WATER.
  
 NOT COMPLIED 9) SUBMIT A SANITARY AND WATER RISER FOR
 ALL THE CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
  
 NOT COMPLIED 10) THE LOCATION OF THE TOILET PAPER
 DISPENSER IN THE ACCESSIBLE TOILET ROOM SHALL COMPLY
 WITH 2014 FBC - ACCESS. SEC.604.7.
  
  
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  