2017-06-20 13:03:562ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17041335
 6/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED. I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTAL.
  
 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17041335
 5/9/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PLANS DO NOT CLEARLY SHOW HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE FAN COIL UNITS. SOME UNITS HAVE
 O/A DUCTS IN THEIR VICINITIES BUT THERE ARE MANY OTHERS
 THAT DO NOT SHOW ANY O/A DUCT CONNECTIONS OR DUCTS IN
 THEIR VICINITIES I.E. WSHP- 24, 231, 232, 363, & 481.
  
 3) O/A DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS ARE NOT OPERATING ARE REQUIRED PER SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 4) REFER TO SECTION C403.2.7.5 AND INDICATE HOW THE AIR
 DISTRIBUTION SYSTEM WAS SIZED AND DESIGNED.
  
 5) PROVIDE A FIRE DAMPER INSTALLATION DETAIL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER