| 2017-06-20 07:16:30 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS (2ND REVIEW): |
| | |
| | 1. PREVIOUS COMMENTS NOT ADDRESSED. SEVERAL LOCATIONS |
| | DO NOT SHOW LIGHTING CONTROL, AND I DO NOT SEE ANY |
| | RECEPTACLE CONTROL. PROVIODE CORRECTIONS. PREVIOUS |
| | COMMENTS AS FOLLOWS: |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND |
| | C405.2.4. |
| | |
| | C405.2.1 MANUAL LIGHTING CONTROLS. |
| | ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| | THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND |
| | C405.2.1.2. |
| | |
| | C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR |
| | THE LIGHTING SERVING THAT AREA. |
| | THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA |
| | SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT |
| | IDENTIFIES THE LIGHTS SERVED |
| | AND INDICATES THEIR STATUS. |
| | |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE |
| | OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL |
| | CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR |
| | LESS ENCLOSED BY FLOOR-TO-CEILING |
| | HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES |
| | SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS |
| | WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR |
| | SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING |
| | ON TO NOT MORE THAN 50 PERCENT POWER. |
| | |
| | |
| | ASHRAE 90.1, 8.4.2 OUTLET CONTROL |
| | 8.4.2 AUTOMATIC RECEPTACLE CONTROL. |
| | AT LEAST 50% OF ALL 125-VOLT, 15-AMP AND 20-AMP |
| | RECEPTACLES, INCLUDING THOSE IN MODULAR PARTITIONS, |
| | INSTALLED IN THESE SPACES: |
| | A. PRIVATE OFFICES |
| | B. OPEN OFFICES |
| | C. COMPUTER CLASSROOMS SHALL BE CONTROLLED BY AN |
| | AUTOMATIC CONTROL DEVICE THAT SHALL USE: |
| | A) A SCHEDULED BASIS WITH TIME-OF-DAY OPERATED |
| | PROGRAMMABLE CONTROL DEVICE ? |
| | FOR NO MORE THAN 25,000 FT2 AND NO MORE THAN ONE FLOOR |
| | PER DEVICE, OR |
| | B) AN OCCUPANT SENSOR THAT TURNS RECEPTACLES OFF WITHIN |
| | 30 MINUTES OF ROOM |
| | BEING VACATED, OR |
| | C) A SIGNAL FROM ANOTHER CONTROL OR ALARM THAT SIGNALS |
| | THE ROOM IS UNOCCUPIED. |
| | EXCEPTIONS: |
| | A) RECEPTACLES FOR EQUIPMENT FOR 24-HOUR OPERATION. |
| | B) SPACES WHERE AUTOMATIC SHUTOFF WOULD ENDANGER LIFE |
| | SAFETY OR SECURITY. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |