Plan Review Notes
Plan Review Notes For Permit 17041335
Permit Number 17041335
Review Stop P
Sequence Number 1
Notes
Date Text
2017-05-17 10:43:241) SUBMIT FIRE SAFING DETAILS FOR THE PLUMBING PIPE
 PENETRATIONS THROUGH THE FLOORS PER FBC SEC.711.5 &
 714.4.1.
 2) SHT. A300, DETAIL A16 - SHOW THE LENGTH AND WIDTH
 DIMENSIONS OF THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET PER 2014 FBC - ACCESS SEC.604.3.
 3) THE INSTALLATION OF THE GRAB BARS IN THE ACCESSIBLE
 TOILET ROOM SHALL COMPLY WITH 2014 FBC-ACCESS.
 SECS.604.5 & 609.4.
 4) SHT. A300 - DETAIL A16 - SHOW THE CLEAR INSIDE
 DIMENSIONS ( LENGTH X WIDTH) OF THE TOILET ROOM. THE
 MINIMUM WIDTH SHALL BE 85 INCHES. 86 INCHES ALLOWS FOR
 TOLERANCE.2014 FBC-ACCESS. SEC.604.3, 604.3.2.
 5) THE MINIMUM CLEARANCE UNDER A LAVATORY SHALL BE 27
 INCHES PER 2014 FBC-ACCESS. SEC. 306.3.1.DETAIL M1 ON
 A300 IS FOR A SINK. SUBMIT A DETAIL FOR THE LAVATORY.
 6) SHT. P201 - PLBG. NOTES #2 - TEMPERED WATER IS
 REQUIRED AT THE LAVATORY PER 2014 FBC- PLUMBING
 SEC.416.5, 607.1.
 7) WATER HAMMER ARRESTORS ARE REQD. WHERE QUICK
 -CLOSING VALVES ARE UTILIZED. 2014 FBC-PLUMBING
 SEC.604.9.
 8) THE PLANS SHOW COLD WATER TO THE DISHWASHER.
 CLARIFY. SUBMIT SPECIFICATIONS FOR THE DISHWASHER IF IT
 IS TO BE SUPPLIED WITH COLD WATER.
 9) SUBMIT A SANITARY AND WATER RISER FOR ALL THE
 CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 10) THE LOCATION OF THE TOILET PAPER DISPENSER IN THE
 ACCESSIBLE TOILET ROOM SHALL COMPLY WITH 2014 FBC -
 ACCESS. SEC.604.7.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  