Plan Review Notes
Plan Review Notes For Permit 17041335
Permit Number 17041335
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-09 12:24:501ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17041335
 5/9/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PLANS DO NOT CLEARLY SHOW HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE FAN COIL UNITS. SOME UNITS HAVE
 O/A DUCTS IN THEIR VICINITIES BUT THERE ARE MANY OTHERS
 THAT DO NOT SHOW ANY O/A DUCT CONNECTIONS OR DUCTS IN
 THEIR VICINITIES I.E. WSHP- 24, 231, 232, 363, & 481.
  
 3) O/A DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS ARE NOT OPERATING ARE REQUIRED PER SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 4) REFER TO SECTION C403.2.7.5 AND INDICATE HOW THE AIR
 DISTRIBUTION SYSTEM WAS SIZED AND DESIGNED.
  
 5) PROVIDE A FIRE DAMPER INSTALLATION DETAIL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  