| Date |
Text |
| 2017-05-18 07:57:48 | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND |
| | C405.2.4. |
| | |
| | C405.2.1 MANUAL LIGHTING CONTROLS. |
| | ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| | THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND |
| | C405.2.1.2. |
| | |
| | C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR |
| | THE LIGHTING SERVING THAT AREA. |
| | THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA |
| | SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT |
| | IDENTIFIES THE LIGHTS SERVED |
| | AND INDICATES THEIR STATUS. |
| | |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE |
| | OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL |
| | CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR |
| | LESS ENCLOSED BY FLOOR-TO-CEILING |
| | HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES |
| | SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS |
| | WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR |
| | SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING |
| | ON TO NOT MORE THAN 50 PERCENT POWER. |
| | |
| | |
| | ASHRAE 90.1, 8.4.2 OUTLET CONTROL |
| | 8.4.2 AUTOMATIC RECEPTACLE CONTROL. |
| | AT LEAST 50% OF ALL 125-VOLT, 15-AMP AND 20-AMP |
| | RECEPTACLES, INCLUDING THOSE IN MODULAR PARTITIONS, |
| | INSTALLED IN THESE SPACES: |
| | A. PRIVATE OFFICES |
| | B. OPEN OFFICES |
| | C. COMPUTER CLASSROOMS SHALL BE CONTROLLED BY AN |
| | AUTOMATIC CONTROL DEVICE THAT SHALL USE: |
| | A) A SCHEDULED BASIS WITH TIME-OF-DAY OPERATED |
| | PROGRAMMABLE CONTROL DEVICE ? |
| | FOR NO MORE THAN 25,000 FT2 AND NO MORE THAN ONE FLOOR |
| | PER DEVICE, OR |
| | B) AN OCCUPANT SENSOR THAT TURNS RECEPTACLES OFF WITHIN |
| | 30 MINUTES OF ROOM |
| | BEING VACATED, OR |
| | C) A SIGNAL FROM ANOTHER CONTROL OR ALARM THAT SIGNALS |
| | THE ROOM IS UNOCCUPIED. |
| | EXCEPTIONS: |
| | A) RECEPTACLES FOR EQUIPMENT FOR 24-HOUR OPERATION. |
| | B) SPACES WHERE AUTOMATIC SHUTOFF WOULD ENDANGER LIFE |
| | SAFETY OR SECURITY. |
| | |