| Notes |
| Date |
Text |
| 2017-05-02 14:48:37 | REVISION DENIED | | | 1) PROVIDE CFM ON ALL SUPPLY GRILLS. | | | 2) MISSING DUCT SIZE ON LAUNDRY ROOM SUPPLY | | | DUCT AND ALL RETURN AIR DUCT. | | | 3) APPLICATION IS FOR A/C CHANGE OUT PLAN | | | CALLS FOR EXISTING CONDENSER. REFER TO SECTION 107 | | | FBC 2014 | | | 4) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | | #3 (LAUNDRY ROOM) 2014 FBR CODE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|