| 2017-12-11 16:32:46 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041277 | | | 12/11/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REVISED ENERGY CALCULATIONS HAVE NOT BEEN PROVIDED | | | FOR UNITS 1A, 1B, 1C, 2D, & 2E. THE PREVIOUS SUBMITTALS | | | WERE VOIDED. | | | | | | 2) THE FLOOR PLAN DRAWING INDICATES 3.0 TON AC SYSTEMS | | | FOR ALL UNITS, HOWEVER THE SCHEDULE INDICATES 2.5 TON | | | SYSTEMS FOR UNITS 1A, 1B, 1C, & 2D. PLEASE NOTE THAT | | | THE REVISED AC CALCULATIONS INDICATE A 3.0 SYSTEM FOR | | | 1B. | | | | | | 3) 3RD REQUEST FOR WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE EXTERIOR CONDENSERS. | | | | | | 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR | | | HANDLERS- SEE SECTION 307. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|