Plan Review Notes
Plan Review Notes For Permit 17041277
Permit Number 17041277
Review Stop G
Sequence Number 4
Notes
Date Text
2017-12-16 12:40:424TH REVIEW
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PREVIOUS GAS COMMENTS: NOT COMPLIED I SUGGEST A MEETING
 TO BE SCHEDULED TO GO OVER COMMENTS PRIOR TO NEXT
 SUBMITTAL.
  
  
  
 2. THE TANKLESS WATER HEATER SHALL BE MOUNTED 4' AWAY
 FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE
 INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC
 107.2.1
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER
 FBC FG 408.4
  
 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT
 SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH
 APPLIANCE . WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. THE FIRST SECTION OF PE PIPE AFTER METER IS SHOWN AS
 3' 10" ON THE RISER AND 25' 8" ON THE FLOOR PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE SIZING TABLES LISTED ON THE PLAN SHT. A-3.1 ARE
 .5 PSI SYSTEMS IN THE CODE BOOK BUT ARE SHOWN AS 2 PSI
 ON THE PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. THE GENERAL NOTES ON SHT P-3.1 REFERENCES LP GAS
 RISER SHOWS NATURAL GAS PLEASE CLARIFY AND REMOVE
 INCORRECT NOTES. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  