| Date |
Text |
| 2017-11-16 12:43:39 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: 3RD REQUEST NOT COMPLIED A NARRATIVE |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A |
| | DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE |
| | FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |
| | 2. PARTIALLY COMPLIED THIS OCCUPANCY SHALL COMPLY WTH |
| | FHA PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT |
| | THAT WAS USED TO COMPLY WITH FHA ALSO SHOW WHICH DESIGN |
| | SPECIFICATION IS USED FOR THE BATHROOMS A OR B . PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. THE BATHROOM IN THE OFFICE IS A COMMON AREA AND |
| | SHALL COMPLY WITH THE FHA AND ANSI 4.22 |
| | |
| | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | |
| | 2ND REVIEW PREVIOUS COMMENTS: |
| | |
| | 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE FIXTURES IN |
| | THE BATHROOMS SHALL COMPLY WITH FHA |
| | |
| | 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO |
| | BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM |
| | GROUP. PER FBC PL 912.1 |
| | |
| | 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN |
| | UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE |
| | CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES. |
| | PER FBC PL 1003.6 |
| | |
| | NEW COMMENT: |
| | |
| | 1. PLEASE LABEL SOIL STACKS ON THE FLOOR PLAN TO MATCH |
| | RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |