| 2017-11-07 14:30:39 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17041277 |
| | 11/7/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE 1ST REVIEW COMMENTS 1-7 WERE NOT ADDRESSED AND |
| | STILL EXIST WITH THE EXCEPTION OF COMMENT #6 WHICH IS |
| | RESCINDED BASED ON SECTION R403.2.2 FBC-14 ENERGY |
| | CONSERVATION. |
| | I HAVE REPRINTED THE COMMENTS BELOW. PLEASE PROVIDE A |
| | NARRATIVE RESPONSE TO HELP EXPEDITE THE REVIEW. |
| | |
| | PLEASE NOTE THAT THE FIRE-RESISTANCE RATINGS OF WALLS |
| | AND CEILINGS IN THE PROPOSED OCCUPOANCY HAVE STILL NOT |
| | BEEN COMPLETELY ESTABLISHED IN THE ARCHITECTURAL AND |
| | LIFE SAFETY PLANS, AND CURRENTLY NO FIRE DAMPERS ARE |
| | SHOWN ON THE PLANS TO PROTECT DUCTS THAT ARE |
| | PENETRATING BOTH THE VERTICAL AND HORIZONTAL |
| | ASSEMBLIES. WHEN THE PLANS ARE REVISED IN ACCORDANCE |
| | WITH THE BUILDING REVIEW COMMENTS, THESE ISSUES WILL BE |
| | ADDRESSED. |
| | |
| | 1) THE ENERGY CALCULATION FORM R405-2014 INDICATES 2.5 |
| | TON SYSTEMS FOR UNITS 1A AND 1B HOWEVER THE SCHEDULE ON |
| | SHEET A-41 INDICATE 3.0 TON SYSTEMS. A) THE CALCS |
| | INDICATE A 2.0 TON SYSTEM FOR THE OFFICE/LAUNDRY BUT |
| | THE SCHEDULE INDICATES A 1.5 TON SYSTEM. |
| | |
| | 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES |
| | INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F |
| | ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD |
| | WHICH SPECIFIES 91 AND 45 DEGREES. |
| | |
| | 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE |
| | PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE |
| | INDICATING SW FOR ALL OF THE UNITS-. UNITS 1A AND 2D |
| | APPEAR TO BE FACING NORTH, AND 1B, 1C, 2E, AND THE |
| | OFFICE/LAUNDRY APPEAR TO BE FACING SOUTH. |
| | |
| | 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR |
| | CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS. |
| | |
| | 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT |
| | SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY |
| | RATINGS, AND ELECTRICAL HEATING DATA. |
| | |
| | 6) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN |
| | COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY |
| | CONSERVATION AND SECTION 602 FBC-14 MECHANICAL. NOTE- |
| | THIS COMMENT IS RESCINDED. |
| | |
| | 7) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION |
| | OF THE EXTERIOR CONDENSERS. |
| | |
| | 8) NEW COMMENT: CLARIFY HOW THE EXHAUST FAN IN THE |
| | LAUNDRY ROOM WAS SIZED AND PROVIDE AN EQUIPMENT |
| | SCHEDULE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |