| 2017-11-17 07:53:05 | E-MAIL SENT TO SKIP: |
| | GOOD MORNING SKIP, |
| | I'VE SPOKEN WITH JOE CANNON IN REGARDS TO FLOOR SOUND |
| | UNDERLAYMENT. PLEASE REVIEW THE ATTACHMENT (PROFLEX |
| | RCU-500) AND THE REFERENCED STANDARDS, I HAVE ATTACHED |
| | THE STANDARD REFERENCE SHEETS FROM OUR CODE BOOK , THE |
| | DELTA IIC STANDARD REFERENCE IN THE PROFLEX DOCUMENT |
| | ASTM E 2179-03 IS NOT A STANDARD REFERENCE IN THE 2014 |
| | FBC-B REFERENCED STANDARDS. WE DO NOT RECONIZE THIS |
| | STANDARD, IT IS NOT A RECONIZED STANDARD IN THE ICC |
| | CODES EITHER. NOTE THE PROFLEX RTU-500 ONLY RECEIVES A |
| | 50 IIC ON A 6 INCH CONCRETE SLAB. |
| | |
| | ATTACHMENT: PROFLEX RCU-500. PDF |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2017-11-03 14:14:40 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17041277 |
| | ADD: 2115 MERCER AVE. |
| | CONT: ERETZOR CONSTRUCTION LLC |
| | TEL: 954-937-7041 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: FRI. NOV. 03/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET A-1: |
| | |
| | 1) COMPLIED. |
| | |
| | 2.) 3RD REQUEST/ SEMI COMPLIED. THE COVERSHEET NOW |
| | INDICATES THE OCCUPANCY TYPE AS R-4, UP TO 90 DAYS, 16 |
| | RESIDENTS AT ANY GIVEN TIME AND 2 STAFF MEMBERS, FULLY |
| | R13 SPRINKLERED BUILDING. WHAT WE ARE HAVING A PROBLEM |
| | WITH ON ALL THE FLOOR PLANS AND NEW LIFE SAFETY SHEETS |
| | A16 & A17 ALL SHOW 19 BEDS NOT THE MAXIMUM OF 16 |
| | PERSONS. THE CODE STATES THERE WE DO NOT COUNT STAFF |
| | NOR DOES THE CODE REQUIRE STAFF TO SLEEP OVER. IT WOULD |
| | APPEAR ROOM 1C NEEDS TO BE DEFINED AS TO USAGE, WHO |
| | WILL USE THIS APARTMENT? IF THIS ROOM IS FOR STAFF |
| | INDICATE AS SUCH. |
| | FOR THIS REVIEW IT IS GOING TO BE ASSUMED UNIT 1C IS A |
| | STAFF ROOM, STAY R-4/ AND FAIR HOUSING, NOT |
| | ACCESSIBILITY. THIS NEEDS TO BE DEFINED ON THE PLANS. |
| | IF THIS IS TO BE A PATIENT SLEEPING QUARTERS THEN THE |
| | OCCUPANT LOAD IS 19 OVER THE ALLOWABLE R4 OCCUPANCY AND |
| | BECOMES A I-1 OCCUPANCY SEE FBC-B 308.3. |
| | |
| | 2ND REVIEW COMMENTS. OCCUPANCY TYPE 301.1 SHORT TERM |
| | FACILITY OR LONG TERM FACILITY. . OCCUPANCY TYPE 301.1 |
| | SHORT TERM FACILITY OR LONG TERM FACILITY. PLEASE NOTE |
| | ON THE COVERSHEET THERE IS A NOTE STATING THIS IS A |
| | SHORT TERM FACILITY. WHEN DEFINING SHORT TERM THE |
| | BUILDING CODE USES 30 DAYS OR LESS FOR SHORT TERM |
| | (TRANSIENT), LONGER STAYS ARE (NON-TRANSIENT). IT |
| | APPEARS THIS USAGE IS MORE OF A R2(WITH MORE THAN 16 |
| | OCCUPANTS) FACILITY AN ALCOHOL AND OR DRUG REHAB CENTER |
| | WITH CONGREGATE CARE FACILITIES, (A BUILDING OR PART |
| | THERE OF THAT CONTAINS SLEEPING UNITS WHERE THE |
| | RESIDENTS SHARE BATHROOMS AND OR KITCHEN FACILITIES. |
| | THE OTHER ISSUE IS WITH THE UNITS CONTAINING 2 BEDROOMS |
| | AND 2 OCCUPANTS PER BEDROOM AND SHARED BATHROOMS AND OR |
| | KITCHEN FACILITIES THE UNIT ALSO RESEMBLES DORMITORIES! |
| | PLEASE DECLARE OCCUPANCY AND USAGE. 2014 FBC-B 302.1 |
| | CLASSIFICATION. |
| | |
| | 3A) COMPLIED. MINIMUM TYPE OF CONSTRUCTION (TABLE 503) |
| | |
| | 3B) 3RD REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3C) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT |
| | ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2 |
| | APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 4) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT |
| | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR |
| | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY |
| | WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 5) COMPLIED. |
| | |
| | 6) 3RD REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B |
| | SECTION 420 IS ACHIEVED. |
| | 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL |
| | COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH |
| | 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE. |
| | |
| | 6A)3RD REQUEST. PLEASE PROVIDE WHERE THERE IS A WALL |
| | SCHEDULE, CUT SECTION THROUGH THE BEDROOM RATED WALLS |
| | SHOWING COMPLIANCE WITH FBC-B 420.2.RATED WALLS BETWEEN |
| | BEDROOMS AND OPENING PROTECTIVES. . 420.2 SEPARATION |
| | WALLS. WALLS SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDING, WALLS SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND WALLS SEPARATING DWELLING OR SLEEPING |
| | UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE |
| | SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS |
| | IN ACCORDANCE WITH SECTION 708. |
| | |
| | 6B) 3RD REQUEST. THE RESPONSE INDICATES ON SHEET A-11 |
| | INDICATES THE USE OF THE HAMBRO FLOOR SYSTEM AND UL |
| | LISTING G525. PLEASE PROVIDE THE ASSEMBLY ON THE SET OF |
| | PLANS SO THE INSPECTOR CAN VERIFY THE COMPONENTS THAT |
| | MAKE UP THE ASSEMBLY. THE FLOOR SYSTEM WILL NEED TO BE |
| | 2 HOUR FIRE RATED ASSEMBLY FROM BOTH SIDES OF THE |
| | ASSEMBLY SINCE THE ASSEMBLY IS NOT SYMMETRIC. PLEASE |
| | REVIEW TABLE 707.3.10 FOR THE 2 HOUR RATING. THE |
| | RESPONSE LETTER INDICATES FBC-B 711.3 ALLOWS FOR THE |
| | ASSEMBLY TO BE ? HOUR. PLEASE REVIEW THE EXCEPTION IS |
| | FOR NFPA 13 SYSTEM UNDER 903.3.1.1. THE FIRE PROTECTION |
| | PLANS INDICATE FIRE SPRINKLERS DESIGNED TO NFPA |
| | 903.3.1.2 OR NFPA 13R. |
| | |
| | 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| | |
| | 6C) SEMI-COMPLIED. THE SUBMITTED FIRE SPRINKLER PLANS |
| | SUBMITTED ARE COLOR PHOTOCOPIED SIGNATURES. [F] 420.4 |
| | AUTOMATIC SPRINKLER SYSTEM. GROUP R OCCUPANCIES SHALL |
| | BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH SECTION 903.2.8. GROUP I-1 |
| | OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.2.6. QUICKRESPONSE OR RESIDENTIAL AUTOMATIC |
| | SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTION 903.3.2. |
| | |
| | 6D)3RD REQUEST. SEMI-COMPLIED. THE LIFE SAFETY PLAN |
| | A-16 THE 1ST FLOOR SHOWS A LAYOUT OF SMOKE ALARM |
| | DEVICES, PULL STATIONS AND EXIT LIGHTS EMERGENCY |
| | LIGHTS. SHEET A16 THE 1ST FLOOR IS MISSING SMOKE |
| | DETECTORS OUTSIDE UNIT 1B BEDROOM HALLWAY & SHEET A17 |
| | THE 2ND FLOOR SHOWS NO SMOKE DETECTORS EITHER INSIDE OR |
| | OUTSIDE OF THE BEDROOM UNITS. 2014 FBC-B 907.1.1 |
| | CONSTRUCTION DOCUMENTS. |
| | [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. FIRE |
| | ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED IN |
| | GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE WITH |
| | SECTIONS 907.2.6, 907.2.8 AND 907.2.9, RESPECTIVELY. |
| | SINGLE-OR MULTIPLE-STATION SMOKE ALARMS SHALL BE IN |
| | ACCORDANCE WITH SECTION 907.2.11. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 9) BUILDING PROVISO/ DEFERRED SUBMITTAL. FBC 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 10) 3RD ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR |
| | HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW |
| | THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3), |
| | CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6), |
| | GUARDS 1013.3, OPENING LIMITATIONS (1013.4), |
| | 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS |
| | SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF |
| | 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. |
| | 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL |
| | THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS |
| | SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50 |
| | POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. |
| | |
| | PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF |
| | MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR |
| | GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF |
| | PLANS. |
| | |
| | 11) 3RD ROUND OF COMMENTS. THE RESPONSE INDICATES THE |
| | UNDERLAYMENT CRITERIA ARE FOUND ON SHEET A-5. |
| | PLEASE PROVIDE THE ACTUAL TEST REPORTS FOR SOUND |
| | UNDERLAYMENT USING THE HAMBRO SYSTEM WITH 3 INCH |
| | CONCRETE SLAB. PLEASE ALSO NOTE THAT FOR EACH FLOORING |
| | TYPE, TILE. AND WOOD SEPARATE TEST ARE REQUIRED. |
| | |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR |
| | SYSTEM/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 11A)3RD REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 11B)3RD REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 11C) 3RD REQUEST. TYPE V CONSTRUCTION: FBC-B-2014 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO |
| | SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |