| Date |
Text |
| 2017-09-27 09:51:01 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: 2ND REQUEST NOT COMPLIED A NARRATIVE |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER WITH A |
| | DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE |
| | FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |
| | 2. THE PLAN DOES NOT INDICATE WHAT TYPE OF OCCUPANCY |
| | THIS PROJECT IS IF IT IS GOING TO BE MULTI FAMILY |
| | RESIDENTIAL AN R3 OR R4 THE GROUND FLOOR UNIT WILL HAVE |
| | TO COMPLY WITH THE FHA DESIGN MANUAL. PLEASE PROVIDE |
| | TYPE OF OCCUPANCY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. THE BATHROOM IN THE EXERCISE ROOM IS A COMMON AREA |
| | AND SHALL COMPLY WITH THE FBC ACC 603,604, 606, 609 |
| | |
| | 4. THE TRANSFER SHOWER IN BATHROOM #1 IN UNIT 1A AND 1B |
| | SHAL BE 36" X 36". PER FBC ACC 608.2.1 |
| | |
| | 5. THE GRAB BARS FOR THE ROLL IN SHOWER IN BATHROOM #1 |
| | IN UNIT 1C SHALL COMPLY WITH. PER FBC ACC 608.3.2 |
| | |
| | 6. SHOW IN ALL ACCESSIBLE BATHROOMS THE CLEAR FLOOR |
| | SPACE FOR THE TOILET , LAVATORY AND SHOWER. PER FBC ACC |
| | 608.2.1 ,608.2.2.1 ,606.2,604.3.1 |
| | |
| | 7. SHOW HEIGHT DIMENSIONS FOR SHOWER SEATS AND |
| | CONTROLS. PER FBC ACC 608.5.1 , 610.3 , 608.5.2 , |
| | 610.3.2, 610.3.1 |
| | |
| | 9. PLEASE PROVIDE WATER RISER DIAGRAM. WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | |
| | NEW COMMENTS: |
| | |
| | 1. GRAB BARS SHALL BE ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 2. SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE SIDE |
| | WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON |
| | THE CONTROL WALL 15 INCHES (380 MM) MAXIMUM FROM THE |
| | CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING. PER |
| | FBC ACC 608.5.1 |
| | |
| | 3. THE SOIL STACKS FROM SECOND FLOOR SHALL CONNECT TO |
| | BUILDING DRAIN DOWN STREAM OF FIRST FLOOR BATHROOM |
| | GROUP. PER FBC PL 912.1 |
| | |
| | 4. SHT. A-3.1 PLEASE EXPAND RISER DIAGRAM IN THE AREA |
| | OF S-5 AND S-4 THE LINES ARE DRAWN ON TOP OF EACH OTHER |
| | I CAN NOT DETERMINE WHAT IS FIRST FLOOR OR 2ND OR WHICH |
| | BATHROOM GROUP IS WHICH PLEASE CLARIFY. WPB AMEND TO |
| | FBC 107.3.5.1.3(13) |
| | |
| | 5. THE RISER SHOWS A 4" PIPE RUNNING TO BATH #2 IN |
| | UNITS 1A AND 1B THE FLOOR PLAN SHOWS A 3" PLEASE |
| | CLARIFY. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 6. A LENT TRAP IS REQUIRED FOR THE WASHING MACHINES. |
| | PER FBC PL 1003.6 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |