| Plan Review Notes For Permit 17041277 |
| Permit Number |
17041277 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-27 10:28:08 | 2ND REVIEW | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC | | | FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @ | | | 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE. | | | | | | 2. THE TANKLES WATER HEATER SHALL BE MOUNTED 4' AWAY | | | FROM ALL OPENINGS PLEASE PROVIDE MANUFACTURE | | | INSTILLATION GUIDE TO VERIFY. PER WPB AMEN TO FBC | | | 107.2.1 | | | | | | 3. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 4. PLEASE PROVIDE SEDIMENT TRAPS AT EACH APPLIANCE. PER | | | FBC FG 408.4 | | | | | | 5. SHOW SYSTEM PRESSURE ON RISER DIAGRAM FOR CLARITY IT | | | SHOWS A REGULATOR AFTER THE METER AND THEN ON AT EACH | | | APPLIANCE . WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|