| Date |
Text |
| 2017-09-27 16:50:09 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17041277 |
| | ADD: 2115 MERCER AVE. |
| | CONT: ERETZOR CONSTRUCTION LLC |
| | TEL: 954-937-7041 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 27/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET A-1: |
| | |
| | 1A) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF |
| | WORK INDICATES NEW BUILDINGS, TWO STORIES WHEREAS THE |
| | TITLE BLOCK INDICATES THIS IS AN INTERIOR REMODEL. |
| | DISCREPANCY IN THE DESCRIPTION OF WORK. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1B)SEMI-COMPLIED. THIS REVIEW THERE IS A INDEX WITHIN |
| | THE COVERSHEET. NEED A UPDATED CODE ANALYSIS FOR THE |
| | BUILDING INFORMATION. WITHOUT THE OCCUPANCY TYPE BEING |
| | DECLARED AND THE MINIMUM BUILDING TYPE DECLARED IT IS |
| | ONLY ASSUMPTIONS, A THOROUGH REVIEW CANNOT BE |
| | ACCOMPLISHED. THE DESIGNER OF RECORD HAS NOT PROVIDED A |
| | CODE ANALYSIS, PROVIDING THE OCCUPANCY TYPE, USAGE, |
| | (ALCOHOL AND OR DRUG CENTER, GROUP HOME), THE TYPE OF |
| | MINIMUM CONSTRUCTION REQUIRED, OR IF FIRE SPRINKLERED. |
| | NOTE FIRE SPRINKLER PLANS FOR R13 SYSTEM SUBMITTED. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | |
| | 2. OCCUPANCY TYPE 301.1 SHORT TERM FACILITY OR LONG |
| | TERM FACILITY. . OCCUPANCY TYPE 301.1 SHORT TERM |
| | FACILITY OR LONG TERM FACILITY. PLEASE NOTE ON THE |
| | COVERSHEET THERE IS A NOTE STATING THIS IS A SHORT TERM |
| | FACILITY. WHEN DEFINING SHORT TERM THE BUILDING CODE |
| | USES 30 DAYS OR LESS FOR SHORT TERM (TRANSIENT), LONGER |
| | STAYS ARE (NON-TRANSIENT). IT APPEARS THIS USAGE IS |
| | MORE OF A R2(WITH MORE THAN 16 OCCUPANTS) FACILITY AN |
| | ALCOHOL AND OR DRUG REHAB CENTER WITH CONGREGATE CARE |
| | FACILITIES, (A BUILDING OR PART THERE OF THAT CONTAINS |
| | SLEEPING UNITS WHERE THE RESIDENTS SHARE BATHROOMS AND |
| | OR KITCHEN FACILITIES. THE OTHER ISSUE IS WITH THE |
| | UNITS CONTAINING 2 BEDROOMS AND 2 OCCUPANTS PER BEDROOM |
| | AND SHARED BATHROOMS AND OR KITCHEN FACILITIES THE UNIT |
| | ALSO RESEMBLES DORMITORIES! PLEASE DECLARE OCCUPANCY |
| | AND USAGE. 2014 FBC-B 302.1 CLASSIFICATION. |
| | |
| | 3) MINIMUM TYPE OF CONSTRUCTION (TABLE 503) |
| | |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | 10) FL. ACCESSIBILITY CODE OR FAIR HOUSING, VERTICAL |
| | ACCESSIBILITY? |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | EQUIPMENT |
| | SPECIAL OCCUPANCY REQUIREMENTS |
| | FAIR HOUSING REQUIREMENTS |
| | |
| | 11. NO FINISH SCHEDULE!!!!INTERIOR REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | SANITATION |
| | |
| | 12.2ND REQUEST. SPECIAL SYSTEMS: |
| | ELEVATORS |
| | LIFTS |
| | FLORIDA ACCESSIBILITY (SHORT TERM/ TRANSIENT) VERSES |
| | FAIR HOUSING (LONG TERM/ NON-TRANSIENT). |
| | |
| | |
| | |
| | 1C) THE PLANS DO NOT INDICATE IF THE CONCEPT FOR THIS |
| | PROJECT TO BE CONSIDERED 1 BUILDING (TOTAL SQUARE FOOT, |
| | FOOT PRINT OR IF THEY ARE TRYING TO COMPLY UNDER THE |
| | BUILDINGS ON THE SAME LOT, SECTION 503.1.2. |
| | |
| | 1D) COMPLIED. R13 FIRE SPRINKLER PLANS. |
| | |
| | 1E) NEW COMMENT. SHEET A2.1 DESIGN LIVE LOADS PLANS |
| | INDICATE: STAIRS & CORRIDORS 60 PSF CORRECT. |
| | 2014 FBC-B TABLE 1607.1(30) STAIRS 100 PSF, |
| | 2014 FBC-B TABLE 1607.1(25) PUBLIC ROOMS & CORRIDORS |
| | 100 PSF |
| | |
| | |
| | 1F) COMPLIED. |
| | |
| | 2) 2ND REQUEST. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) 2ND REQUEST, SEE MECHANICAL COMMENTS. PLEASE SUBMIT |
| | ENERGY CALCULATIONS. 2014 FBC-ENERGY CODE. C401.2 |
| | APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 4) 2ND REQUEST. ART IN PUBLIC PLACES. THE CITY OF WEST |
| | PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT |
| | THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT |
| | FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY |
| | WITH THIS ORDINANCE. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 5) COMPLIED. |
| | |
| | 6) 2ND REQUEST. PLEASE SHOW HOW COMPLIANCE WITH FBC-B |
| | SECTION 420 IS ACHIEVED. |
| | 420.1 OCCUPANCIES IN GROUPS I-1, R-1, R-2 AND R-3 SHALL |
| | COMPLY WITH THE PROVISIONS OF SECTIONS 420.1 THROUGH |
| | 420.5 AND OTHER APPLICABLE PROVISIONS OF THIS CODE. |
| | |
| | 6A)2ND REQUEST. RATED WALLS BETWEEN BEDROOMS. 420.2 |
| | SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS IN |
| | THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN |
| | THE SAME BUILDING AND WALLS SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 708. |
| | |
| | 6B) 2ND REQUEST. 420.3 HORIZONTAL SEPARATION. FLOOR |
| | ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS |
| | IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH |
| | SECTION 711. |
| | |
| | 6C) COMPLIED. [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. |
| | GROUP R OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE |
| | EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE WITH SECTION 903.2.6. QUICKRESPONSE OR |
| | RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.2. |
| | |
| | 6D) [F] 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. |
| | FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED |
| | IN GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE |
| | WITH SECTIONS 907.2.6, 907.2.8 AND 907.2.9, |
| | RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE ALARMS |
| | SHALL BE IN ACCORDANCE WITH SECTION 907.2.11. |
| | |
| | 7A) 2ND REQUEST. THE COVERSHEET NOW INDICATES WIND |
| | DESIGN. THE COVERSHEET UNDER THE WIND DESIGN INDICATES |
| | A BASIC WIND SPEED OF 160 MPH, THEN 2 LINES DOWN A WIND |
| | SPEED IN 3 SECOND GUST OF 140 MPH. THEN ON SHEET A2.1 |
| | WIND SPEED OF 170 MPH. PLEASE SEE THE 2014 FBC-B FIGURE |
| | 1609A FOR BUILDINGS WITH A RISK CATEGORY II. THE FIGURE |
| | SHOWS THE CITY OF WEST PALM BEACH IN A WIND ZONE OF 170 |
| | VULT/ 3 SECOND GUST. THE WIND SPEED CONVERSION TABLE |
| | 1609.3.1 INDICATES FOR 170 VULT THE CONVERSION TO VASD |
| | WILL BE 132 VASD/ 3 SECOND GUST. PLEASE CORRECT. |
| | 1ST ROUND OF COMMENTS. SHEET A8 & A9 SHOW PRESSURES FOR |
| | COMPONENTS AND CLADDING, BUT THERE IS NO WIND DESIGN |
| | CRITERIA TO KNOW IF THESE PRESSURES ARE ACCURATE. 2014 |
| | FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 7.2. RISK CATEGORY. |
| | |
| | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 8) 2ND REQUEST, UNTIL THE WIND DESIGN PRESSURES ARE IN |
| | DESIGN PRESSURES (VASD) THE PRODUCT APPROVALS SUBMITTED |
| | CANNOT BE CHECKED FOR CODE COMPLIANCE UNTIL THE WIND |
| | DESIGN IS FINALIZED. |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 10) 2ND ROUND OF COMMENTS. SHEET A15.1 SHOW POST FOR |
| | HANDRAIL ANCHORING. THE PLANS SUBMITTED DOES NOT SHOW |
| | THE HANDRAIL HEIGHT (1012.2) GRASPABILITY (1012.3), |
| | CONTINUITY (1012.4) EXTENSIONS IF REQUIRED (1012.6), |
| | GUARDS 1013.3, OPENING LIMITATIONS (1013.4), |
| | 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS |
| | SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF |
| | 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. |
| | 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS (ALL |
| | THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL FILLERS |
| | SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD OF 50 |
| | POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. |
| | |
| | PLANS ARE DEFICIENT IN STAIR DESIGN AS TO TYPE OF |
| | MATERIAL, LOADING PER SQ. FT. THERE IS NO HANDRAIL OR |
| | GUARDRAIL DESIGN WITHIN THE PERMIT PACKAGE SET OF |
| | PLANS. |
| | |
| | 11) 2ND ROUND OF COMMENTS. THE PLANS DO NOT INDICATE |
| | WHAT THE 2ND FLOOR FINISHES WILL BE? PLEASE SHOW |
| | COMPLIANCE WITH: |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A HAMBRO FLOOR |
| | SYSTEM/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 11A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 11B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 11C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 13) THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY, COLLATE AND STAPLE INTO |
| | SETS OF PLANS. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |