| 2017-05-02 16:44:06 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17041277 |
| | 5/2/17 |
| | |
| | 1) THE MECHANICAL PLANS ARE INCOMPLETE. PLEASE PROVIDE |
| | THE FOLLOWING: |
| | |
| | A) AC COOLING HEATING CALCULATIONS- SECTION C403.2.1 |
| | FBC-14 ENERGY CONSERVATION. |
| | B) ENERGY CALCULATIONS- SECTIONS C101.3, C101.5, AND |
| | C401.2 FBC-14 ENERGY CONSERVATION. |
| | C) MINIMUM VENTIALTION CALCULATIONS FOR ALL OCCUPIED |
| | ROOMS AND SPACES. PROVIDE A TABLE THAT INCLUDES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR- TABLE 403.3 |
| | FBC-14 MECHANICAL. |
| | D) EXHAUST VENTILATION CALCULATIONS FOR THE RESTROOMS- |
| | TABLE 403.3 |
| | E) COMBUSTION AIR CALCULATIONS AND VENTING PLANS FOR |
| | THE GAS DRYERS - SECTION 304 AND 501.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | F) COMPLETE DUCT LAYOUT AND AIR DISTRIBUTION PLANS |
| | SHOWING DUCT SIZES, DIFFUSER AND RETURN GRILL SIZES, |
| | TRANSFER GRILLS OR DUCTS WHERE REQUIRED, AND CFM'S AT |
| | EACH DEVICE. |
| | G) COMPLETE AC EQUIPMENT SCHEDULES THAT INDICATE THE |
| | MAKES AND MODELS OF THE COMPONENTS, COOLING AND HEATING |
| | CAPACITIES, SUPPLY CFMS, EFFICIENCY RATINGS, AND |
| | ELECTRICAL DATA. |
| | H) WIND LOAD ENGINEERING FOR INSTALLATION OF THE |
| | EXTERIOR CONDENSERS. |
| | |
| | 2) SHEET A-4.1: THE PLAN APPEARS TO SHOW AIR HANDLERS |
| | IN THE ATTIC SPACES ABOVE THE HALLWAY IN THE MAIN |
| | BUILDING, AND IN THE OFFICE WHICH IS PROHIBITED PER |
| | SECTION C403.2.7.6 FBC-14 ENERGY COMPLIANCE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |