| Plan Review Notes For Permit 17041276 |
| Permit Number |
17041276 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-05-09 16:43:35 | PROVISO ITEMS ON PLAN: | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 (NOT PROVIDED, WE WILL ACCEPT THIS AS | | | A DEFERRED SUBMITTAL WITH A NOTE ON PLAN INDICATING | | | THAT THE CALCULATION WILL BE PROVIDED BEFORE FINAL.) | | | 2. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8 (RECEPTACLES FOR WATER | | | HEATERS AND A/C'S NEED GFCI ALSO) | | | 3. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN | | | PENINSULA. NEC 210.8, 210.52(C)(3) (NOT PROVIDED) |
|