Plan Review Notes
Plan Review Notes For Permit 17041276
Permit Number 17041276
Review Stop E
Sequence Number 4
Notes
Date Text
2018-05-09 16:43:35PROVISO ITEMS ON PLAN:
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED, WE WILL ACCEPT THIS AS
 A DEFERRED SUBMITTAL WITH A NOTE ON PLAN INDICATING
 THAT THE CALCULATION WILL BE PROVIDED BEFORE FINAL.)
 2. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8 (RECEPTACLES FOR WATER
 HEATERS AND A/C'S NEED GFCI ALSO)
 3. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA. NEC 210.8, 210.52(C)(3) (NOT PROVIDED)