| 2018-04-16 14:25:18 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| | FBC 107.2.1 |
| | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE FOR |
| | NON-RESIDENTIAL AREAS. FOR RESIDENTAIL AREAS, PROVIDE |
| | NOTE FOR COMPLIANCE: PROVIDE COMPLIANCE: "A MINIMUM OF |
| | 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY |
| | LAMPS". FBC EC 405.5.2 |
| | 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS |
| | ONCE AT THE PANELS, AND THEN AGAIN FOR THE NUMBER OF |
| | UNITS FOR THE SERVICE. DEMAND FACTORS CAN ONLY BE |
| | APPLIED ONCE. SEE CODE SECTION FOR EXPLANATION. NEC |
| | 220.84 |
| | 7. RISER DIAGRAM SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| | IN THE CONDUIT TO FPL FROM THE METER BASE. THIS CONDUIT |
| | SHOULD NOT HAVE AN EGC. PROVIDE CORRECTION. NEC 250.6 |
| | 8. RISER SHOWS ONE GROUND ROD. SERVICE GROUNDING |
| | ELECTRODE NEEDS TO BE AUGMENTED BY AN ADDITIONAL |
| | ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE EVIDENCE OF |
| | RESISTANCE TO GROUND OF 25 OHMS OR LESS. PROVIDE |
| | CORRECTION. NEC 250.56 |
| | 9. ALL RECEPTACLES IN KITCHEN FOR COUNTER TOP USE |
| | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 10. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8 |
| | 11. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN |
| | PENINSULA. NEC 210.8, 210.52(C)(3) |
| | 12. PROVIDE CORRECT ADDRESS WITH CORRECT STREET NAME ON |
| | PLAN. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |