Plan Review Notes
Plan Review Notes For Permit 17041276
Permit Number 17041276
Review Stop E
Sequence Number 3
Notes
Date Text
2018-04-16 14:25:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE FOR
 NON-RESIDENTIAL AREAS. FOR RESIDENTAIL AREAS, PROVIDE
 NOTE FOR COMPLIANCE: PROVIDE COMPLIANCE: "A MINIMUM OF
 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS". FBC EC 405.5.2
 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS
 ONCE AT THE PANELS, AND THEN AGAIN FOR THE NUMBER OF
 UNITS FOR THE SERVICE. DEMAND FACTORS CAN ONLY BE
 APPLIED ONCE. SEE CODE SECTION FOR EXPLANATION. NEC
 220.84
 7. RISER DIAGRAM SHOWS AN EQUIPMENT GROUNDING CONDUCTOR
 IN THE CONDUIT TO FPL FROM THE METER BASE. THIS CONDUIT
 SHOULD NOT HAVE AN EGC. PROVIDE CORRECTION. NEC 250.6
 8. RISER SHOWS ONE GROUND ROD. SERVICE GROUNDING
 ELECTRODE NEEDS TO BE AUGMENTED BY AN ADDITIONAL
 ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE EVIDENCE OF
 RESISTANCE TO GROUND OF 25 OHMS OR LESS. PROVIDE
 CORRECTION. NEC 250.56
 9. ALL RECEPTACLES IN KITCHEN FOR COUNTER TOP USE
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 10. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 11. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA. NEC 210.8, 210.52(C)(3)
 12. PROVIDE CORRECT ADDRESS WITH CORRECT STREET NAME ON
 PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER