Plan Review Notes For Permit 17041276
Permit Number 17041276
Review Stop M
Sequence Number 2
Notes
Date Text
2017-09-19 16:27:341ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041276
 9/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AC AND ENERGY CALCULATIONS HAVE BEEN SUBMITTED AS
 REQUESTED, HOWEVER OF THE FOUR END UNITS ON THE 1ST AND
 2ND FLOOR, CALCULATIONS FOR ONLY TWO OF THE UNITS HAVE
 BEEN SUBMITTED.
  
 2) THE SUMMER AND WINTER OUTSIDE DRYBULB TEMPERATURES
 INDICATED ON THE AC CALCULATIONS AT 94 AND 35 DEGREES F
 ARE NOT IN COMPLIANCE WITH THE ACCA/ASHRAE STANDARD
 WHICH SPECIFIES 91 AND 45 DEGREES.
  
 3) THE FRONT DOOR DIRECTIONAL ORIENTATIONS SHOWN ON THE
 PLANS DO NOT MATCH THE AC CALCULATIONS WHICH ARE
 INDICATING SW FOR ALL OF THE UNITS.
  
 4) SHEET A-14: 2ND REQUEST FOR COMBUSTION AIR
 CALCULATIONS AND VENTING PLANS FOR THE GAS DRYERS.
  
 5) A-14: 2ND REQUEST FOR COMPLETE AC EQUIPMENT
 SCHEDULES THAT INDICATE TOTAL SUPPLY CFMS, EFFICIENCY
 RATINGS, AND ELECTRICAL HEATING DATA. PLEASE NOTE THAT
 THE SCHEDULE IS INDICATING OFFICE/LAUNDRY HOWEVER THERE
 IS NO OFFICE ON THE PLANS- PLEASE CORRECT.
  
 6) EXHAUST VENTILATION IS REQUIRED FOR THE KITCHENS AND
 THE COOKING APPLIANCES., HOWEVER NO INFORMATION HAS
 BEEN PROVIDED ON THE PLANS. REFER TO SECTION 505 AND
 SHOW COMPLIANCE ON THE PLANS.
  
 7) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND SECTION 602 FBC-14 MECHANICAL.
  
 8) 2ND REQUEST WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE EXTERIOR CONDENSERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  